Laserfiche WebLink
IT T S Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> MAR 1 7 1°92 TEST RESULTS <br /> ENVIR ! 'N AL 14EALTN -'---- <br /> FERMIf/SERVi1,ES June 12, 1989 <br /> Mr. Gerrit Van Riet <br /> De Boer Truck Lines, Inc. <br /> P. 0. Box 635 SITE: 201 West 5th Street <br /> Ripon, California 95366 Ripon, California <br /> Dear Mr. Van Riet: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank (s) . <br /> Enclosed are copies of test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight , according to the current <br /> -rules , if the loss or gain is less than . 05 gallons per one hour <br /> of testing . - If the results are beyond these parameters , you <br /> should consider taking some remedial action . <br /> TA 149. k/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATIO14 CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 6,000 Diesel -.04219 Yes <br /> South 8,000 Diesel -.04286 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> ( r <br /> rank Keser <br /> Certified T ster <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />