ITTSIntegrity Tank Testing Systerr, Inc. <br /> iLz <br /> MAR 1 7 1992 <br /> ENVIRONNION"! W_ <br /> TEST DATA AND <br /> TEST RESULTS <br /> June 7, 198E <br /> . Gerrit Van Reit <br /> De Boer Truck Lines, Inc . <br /> P . 0 . Box 635 <br /> Ripon, California 95366 <br /> Dear Mr . Van Reit ; <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight, according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK !I/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 6, 000 Diesel - . 04072 Yes <br /> South 8, 000 Diesel - . 02952 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> —�� <br /> Frank Kese <br /> Certified Vster <br /> 800 262-8378 166 FYciak West Circle Stockton, CA 95206 (209) 466-8036 <br />