Laserfiche WebLink
ITTSIntegrity Task Testing Systems, Inc. <br /> July 11, 1991 <br /> Mr. Gerrit Van Riet <br /> DE BOER TRUCK LINES, INC. <br /> P. O. Box 635 <br /> Ripon, California 95366 <br /> Site: 201 West Fifth <br /> Ripon, California <br /> Dear Mr. Van Riet: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank. <br /> Enclosed are copies of the test worksheets, graphs, and/or <br /> computer summation for your submittal to the appropriate <br /> governmental agency. Individual computer generated readings <br /> will be forwarded as requested. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 6 , 000 Diesel - .029 Yes �— <br /> South 8, 000 Diesel +.018 Yes <br /> Please contact us if you need additional assistance or <br /> information, <br /> Sincerely, <br /> �t%iG�pt�,�� <br /> W. N. Savage <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />