Laserfiche WebLink
ITIS <br />August 21, 1991 <br />Integrity Tank Testing Systems, Inc. <br />Mr. Tim Maeder <br />Valley Wholesale Drugs <br />P. O. Box 2065 <br />Stockton, California 95201 <br />Site: 1401 West Fremont <br />Stockton, California <br />Dear Mr. Maeder: <br />Following is a summary of the precision testing we recently <br />conducted on your underground storage tank. <br />Enclosed are copies of the test worksheets, graphs, and/or <br />computer summation for your submittal to the appropriate <br />governmental agency. Individual computer generated readings <br />will be forwarded as requested. <br />A tank system may be considered tight, according to the <br />current regulations if the the test results shown below do <br />not exceed 0.05 gph. If the results are beyond this <br />parameter, an unauthorized release may have occurred, and <br />you should consider taking remedial action. <br />TANK # OR TANK <br />LOCATION CAPACITY <br />North 1,000 <br />South 1,000 <br />Please contact us <br />information. <br />Sincerely, <br />W. N. S <br />Certified Tester <br />PRODUCT <br />TEST <br />CONTAI14ED <br />RESULTS <br />U/L Gas <br />-.013 <br />U/L Gas <br />-.029 <br />if you need <br />additional <br />WITHIN TIGHT <br />TANK PARAMETERS <br />Yes <br />Yes <br />assistance or <br />800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />