Laserfiche WebLink
IT T S Integrity Tank Testing Syste.- C- <br /> November 27 , 1989 <br /> Mr. Randy Thomas <br /> PORT OF STOCKTON FOODS <br /> P. 0. Box 30 Site : 1950 East Miner <br /> Stockton, California 95201 Stockton, California <br /> Dear Mr. Thomas : <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank (s) . <br /> Endlosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate <br /> governmental agency. <br /> A tank system is considered tight, according to the <br /> current rules, if the gain/loss is less than .05 gallons per <br /> one hour of testing. If the results are beyond these <br /> parameters, you should consider taking some remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North of <br /> warehouse 2 , 000 Diesel - .017 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> a/' I �� <br /> FWjC Kes r <br /> Certified so <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466.8036 <br />