Laserfiche WebLink
i' <br /> SITE PLAN GENERAL NOTES SITE PLAN KEYED NOTES <br /> 1 . INSULATION OF CONDUCTORS IN AND UNDER GASOLINE PUMP AREA 1❑ AREA WITHIN OUTLINE IS A CLASS 1 , DIVISION 2 HAZARDOUS AREA, <br /> SHALL BE LISTED AND APPROVED FOR GASOLINE/OIL RESISTANT TYPE. AND SHALL CONFORM TO NEC ART, 500, 501, 514, AND NEPA 30A. <br /> ALL CONDUITS ENTERING OR LEAVING THIS AREA SHALL HAVE <br /> 2. VERIFY EXISTING SITE CONDITIONS, SERVICE REQUIREMENTS AND EXACT SEAL-OFF FITTINGS ON BOTH ENDS OF THE RUN. <br /> LOCATIONS OF SERVICE FACILITIES BEFORE SUBMITTING BID. <br /> 3. ELECTRICAL CONTRACTOR SHALL FURNISH TEMPORARY CONSTRUCTION [:2] NEW FUEL DISPENSER (3-PRODUCT). ONE (1) EXPLOSION PROOF <br /> J-BOX FURNISHED BY DISPENSER MANUFACTURER. CONTRACTOR <br /> POWER WHERE REQUIRED. TO MAKE CONNECTION WITH SEAL-OFF FITTING AT BOTH ENDS OF <br /> 1 4, ALL SITE CONDUCTORS SHALL BE #10 THWN CU., UNLESS NOTED THE RUN. VERIFY REQUIREMENTS, AND COMPLY. <br /> 1 1 OTHERWISE. 3❑ (1) 3/47C FROM EACH DISPENSER TO POWER PANEL GUTTER IN <br /> 1 1 5. CONTRACTOR SHALL VERIFY QUANTITY AND SIZE OF ALL CONTROL WIRES. UTILITY ROOM. VERIFY REQUIREMENTS, <br /> 1 I I 6. MINIMUM SITE, CONDUIT SIZE SHALL BE 3/4" U.O.N.. PROVIDE PULL- ® 3/4^C-2#10 + 1#10 GROUND TO ELECTRICAL PANEL THROUGH PUMP <br /> WIRE IN ALL CONDUIT ONLY (C.O.) RUNS. USE RGS UNDERGROUND RELAY STARTER. VERIFY ALL REQUIREMENTS. <br /> I AND AT DISPENSERS. USE RGS WHERE EXPOSED AND SUBJECT TO <br /> i 1 PHYSICAL ABUSE. USE RGS, EMT, OR FLEXIBLE CONDUIT IN BUILDING ❑ PROVIDE J-BOX FOR ANNULAR SPACE MONITOR. CONTRACTOR TO <br /> 1 EXISTING TRANSFORMER 1 USE LIQUIDLIGHT FLEX AT CONNECTION TO MOTORS. VERIFY REQUIREMENTS. <br /> TO 1 - - (# ® PROVIDE J-BOX FOR TANK LEVEL SENSOR. CONTRACTOR TO VERIFY <br /> I (EX.) 200A METER REQUIREMENTS. <br /> & MAIN (120/208V, 7❑ PROVIDE J-BOX FOR TURBINE POWER. <br /> 1 3-0, 4-W, NEMA 3R) y <br /> - TO REMAIN 9 [_] EXTERIOR LIGHTING CONTROL DIAG. PROVIDE J-BOX AT PIPING SUMP LOCATION. <br /> I R. EX ) MAIN PANEL — <br /> OFFICE �A TO REMAIN I 9 _ 15 9❑ (1) 3/47C TO MAIN FUEL CONTROL PANEL GUTTER IN UTILITY ROOM. <br /> 1 t (EX.) TELEPHONE 1 I VERIFY REQUIREMENTS. <br /> CABINET TO REMAIN �- 3/4"C-2#10 MANUAL 10 NEW CANOPY HID DOWN LIGHT (40OW, 120V, METAL HALIDE). FIXTURES <br /> 11 UTILITY I NEW) PANEL "P" I + GND SWITCH ® SUPPLIED BY ULTRAMAR: <br /> W 1 FUEL DISPENSERS)..::::;;; ;i:>;: iii;;:;;i...................: iii::i;i;;`;;;I:,. B-9 CASHIER 1 1 CONDUIT FOR CANOPY It.,;,, ❑ 0 CA OP FASCIA PERIMETER LIGHTS TO RUN ALONG <br /> _ CKT. A- 1 — <br /> _.:.:`.", :-;: `':'":::... ;;.:q::::::::. ::::::::::.-::.-:::::::::::::::::::. ...:: .. 3 4"C 2 10 3 NEUTRAL <br /> � I l <br /> """ ""` ' " ` """ / # C CANOPY COLUMN WITHIN THE VENEER. VERIFY REQUIREMENTS WITH <br /> _._... ,;;;;;,• FUEL CONTROL,.&:;;: : t:> + GND � EXISTING AIR <br /> COOLER MONITORINGUNIT " >y::;?': & WATER UNIT ULTRAMAR ENGINEER. <br /> CLUSTER.,. is r:'' l`iii: :b::.................... ...... TO REMAIN n I I <br /> }., , 12 (1) 3/47C TO CASHIER AREA FROM INTERCOM BOX AT EACH CANOPY <br /> 5 17 2 COLUMN WITHIN THE VENEER. VERIFY REQUIREMENTS. <br /> 9 1 <br /> 1 I ae A-22,24 <br /> D (EX.) PANEL "B 3/4'C_2#ip-7 EXTERIOR 13 CONDUITS FOR CANOPY HID LIGHTS TO RUN ALONG CANOPY COLUMN <br /> _ _ _ SALES TO REMAIN :>s»>: _ _ + GND SUPREME LTG. & I F "1 EXTERIOR WITHIN THE VENEER. VERIFY REiQUIREMENTS. <br /> I ` — (UNDER COUNTER — 9 E SIGN CKTS %� LIGHTS & <br /> I i^'� ) LY 1 ' �p I PANEL n SIGNS 14 NEW AREA POLE LIGHT FIXTURE (40OW, 120V, METAL HALIDE). <br /> 3/4' C 2#10 — B-?t30 B-5,7 9 1 �A^ & „B,) " . <br /> CONTRACTOR TO VERIFY WITH ULTRAMAR ENGINEER. <br /> 1 + G I 1 3 ': ;: 3/4! 6-3#1 " 5 k 7 <br /> 3/4' C-3#10:;. 12 K 6 ` 5 15 PROVIDE WEATHERPROOF J-BOX FOR HASSTECH PROCESSING & <br /> W i I i2 I + GND mm + GND I A-18,20 n COLLECTION UNIT. PROVIDE (1)3/4"CONDUIT WITH PULL-WIRE <br /> _ : _ / 3/4"C- #10 B TO WIREWAY IN UTILITY ROOM. VERIFY WITH ULTRAMAR N <br /> W ( I I I 1 CASHIER ( g + GND R I ( W UL RAMA ENGINEER). <br /> - J I 1 16 PROVIDE WEATHERPROOF EMERGENCY SHUT-OFF SWITCH FOR FUELING <br /> J 1 I I 11 13 I B-22'24 I 13 11 ® 9 \ PLUS 3/4"C-2#10 ❑ DISPENSING UNITS. PROVIDE SIGN LABELED AS "EMERGENCY <br /> 1 t 3 8-13,15 3/4 C-3#10''.':` 5 7 I + ONO <br /> 1 I I 3/4"C-3#10 + GND I -14,16 �¢� 6 5 I SHUT-OFF SWITCH' POSTED ABOVE SWITCH. (VERIFY LOCATION). <br /> + GND 3/4"C- #tOJ - I �— <br /> 1 12 + GND �j 8 I ❑ PROVIDE CONTACTOR WITH MANUAL ON-OFF SWITCH FOR EXTERIOR 17 PROVIDE NEW FUEL CONTROL & MONITORING UNITS TO REPLACE <br /> 12 Pe E LIGHTING AND SIGN CIRCUITS. VERIFY REQUIREMENTS WITH ULTRAMAR EXISTING WHERE REQUIRED. VERIFY WITH ULTRAMAR ENGINEER. <br /> NEIN CANOPY _ <br /> 1 t NEW CANOPY;:,'-�I ��, ( ® ��I I ENGINEER. <br /> EMERGENCY <br /> W SWITCH <br /> SHUT 1 � ❑ 7 � REG. 19 <br /> i I 10 �/ 7 6 5 <br /> 3 9 <br /> I <br /> ( >• UTILITY COMPANY <br /> I 2 — --- NEW MULTI-PRODUCT '' ' 2 <br /> ;:;r1 <br /> { :; " FUEL. DISPENSER : ii :?::.. UNDERGROUND <br /> I (TYP. OF 4) FUEL STORAGE <br /> 1 I TANK (TYP OF 3) ELECTRICITY: PACIFIC GAS & ELECTRIC (PG&E) <br /> I <br /> t <br /> I <br /> SERVICE PLANNING DEPARTMENT <br /> •. 4040 WEST <br /> LANE <br /> 1 <br /> STOCK'( N CA 9 204 <br /> I 0 5 <br /> I 1 , <br /> 1 I <br /> I 1 <br /> 1 1 SERVICE PLANNER: <br /> SANDY CRANE ® (209) 942-1461 <br /> B-11 1 <br /> 1 I 3/,1%-2#10 NEW AREA <br /> + GND <br /> 14 POLE LIGHT 1 <br /> 3/4"C-2#10 Z 3/4"C-2#10 (TYP.) <br /> + GND <br /> 1 —— 11 <br /> I -- ---------- --- »--------------- -------- <br /> `rrriirr rnr �rlrrr �� rw� r�lllrr � �rrr �� rr r1r �� wer �� rr r <br /> r <br /> O <br /> EXISTING PRICE <br /> EXISTING BEACON <br /> SIGN TO REMAIN SIGN TO REMAIN <br /> 10 5 0 10 20 <br /> 1" ._ 10 0" <br /> WAMW <br /> SCALE FEET <br /> REVISIONS <br /> HAMMER LANE SOUTHWEST GROUP N0. DATE BY COMMENTS <br /> i 't r a m a r <br /> Engineering Consulting Services ------ --- - - ---- 525 WEST THIRD STREET, HANFGRD, CALIFORNIA 93230 <br /> 3972 Barranca Pkwy • Suite J-298 • Irvine ^ CA 92714 - <br /> ' Tel 714 851 -3185 • Fox 714 851 -3016 <br /> DESIGNED: __ __-.-_ _ - ELECTRICAL SITE PLAN <br /> Q y- FESS IGy� R.M.L. <br /> M <F Pyc/ DRAWN BY: PLANS PREPARED BY: 1210 HAMMER LANE & KATHLEEN DRIVE <br /> ELECTRICAL SITE PLAN 1HINON �E 014840 CHECKED By: C.A.D. A 8c S ENGINEERING <br /> STOCKTON, CALIFORNIA <br /> SCALE: 1"=10'-Y, t� EXP. 6-30-99 R.M.L. <br /> PLANNING ENGINEERING CONSTRUCTION MANAGEMENT SCALE: S.S. # <br /> * PROJECT N0. 207 W. ALAMEDA AVENUE, SURTE 203 t" =1D'-D" 641 <br /> sr �fCTR��P�° 51007 BURBANK, CALIFORNIA 91502 DATE: 12-26-95 DRAWING NO. E-2 <br /> qrf OP CA��FD� FILE N0. PHONE: 818-842-3644 FAX: 818-842-3760 <br /> 51007E2 SHEET l OF ( � <br />