• • Page 3 of 11 <br /> 2. SECONDARY PIPE TESTING <br /> Test Method Developed By: ❑ Piping Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ®Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: <br /> Piping Run#87 Piping Run#91 Piping Run# Piping Run#V/R <br /> Syphon <br /> Piping Material: Plastic Plastic Fiberglass Fiberglass <br /> Piping Manufacturer: Flex Flex Smith Smith <br /> Piping Diameter: 2" 2" 3" 4" <br /> Length of Piping Run: Approx 200' Approx 200' Apprqx 15' Approx 200' <br /> Product Stored: 87 prod 91 prod 87 Syphon V/R and Vent <br /> Method and location of Test boot in sump Test boot in sump Test boot in sump Test boot in sump <br /> piping-run isolation: <br /> Wait time between applying 30 minutes 30 minutes 30 minutes 30 minutes <br /> pressure/vacuum/water and <br /> starting test: <br /> Test Start Time: Visual Fail 9:30am 9:30am 10:11am <br /> Initial Reading(Rj): 5 psi 5 psi 5 psi <br /> Test End Time: 10:30am 10:30am 11:11am <br /> Final Reading(RF): 5 psi 5 psi 5 psi <br /> Test Duration: 1 hour 1 hour 1 hour 1 hour <br /> Change in Reading(RF-Rj): 0 0 0 <br /> Pass/Fail Threshold or 0.00 0.00 0.00 0.00 <br /> Criteria: <br /> Test Result: ❑ Pass ®Fail 1 ® Pass ❑Fail I ® Pass ❑Fail ® Pass ❑Fail <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up forfailed tests) <br /> 87 prod sec line—leak at test boot in UDC 7/8,9/10& 11/12 <br />