Laserfiche WebLink
0 • <br /> Mag Sump Sensor Installation Guide Installation Procedure <br /> Sensor Wiring <br /> 1. Firmly hold the top of the sensor, and attach the sensor cable connector into the receptacle in the top of the <br /> sensor. Be sure the connector is attached securely by tightening the locking nut. <br /> 2. Install the cord grip supplied with the cable seal kit in the pan/sump junction box in which the field wiring from <br /> the console terminates. <br /> 3. Coil up the excess cable and tie wrap it out of the way. Feed the two-lead end of the sensor cable through the <br /> cord grip in the junction box.Tighten the cord grip nut to ensure a watertight seal at the cable entry. <br /> 4. Using wire nuts, connect the two-wire cable to the field wires from the console as shown in Figure 4. <br /> I i I i _ • Black <br /> I I <br /> TO i Seal-off i i From <br /> Console i i i i Mag Sump Sensor <br /> I i I I + • White <br /> I I I I <br /> �1/2" rigid <br /> conduit <br /> Epoxy sealed connections in a <br /> sensomWagsensomineps weatherproof junction box <br /> Figure 4. Field Wiring Connections(Observe Polarity) <br /> 5. Seal wire nuts with epoxy sealant following the instructions in Figure 5. <br /> 6. Push the epoxy sealed bag into the junction box. Replace and tighten the junction box cover. <br /> 7. The Mag Sump sensor connects to a Smart Sensor module in the TLS-3XX Console or to a USM module in <br /> the TLS-4XX Console-observe polarity. <br /> 5 <br />