Laserfiche WebLink
Mechanical / Electronic Leak Detector Test <br /> Site: Test Company <br /> Shell 1-5 Pinnacle Fuel Compliance <br /> 717 W. Eighth St. P.O. Box 32849 <br /> San Jose, CA 95152 <br /> Stockton, Ca. 95206 (408)206-9840 <br /> Test Information <br /> 1 2 3 4 <br /> Product #1-Reg #2-Prem #3-Diesel <br /> Manufacturer Veederoot VMI Veederoot <br /> Model FX1V LD2000 FX1DV <br /> Full Operating Pressure (psi) 38 38 38 <br /> Line Bleed Back (ml) 125 140 100 <br /> Trip Time (sec) 3 5 2 <br /> Metering Pressure 12 26 12 <br /> F/E Holding Pressure (psi) 27 37 25 <br /> Test Leak Rate (ml/min)(gph) 189 189 189 <br /> PASS or FAIL I PASS PASS PASS <br /> This form certifies that the annual line leak detector tests were performed at the above referenced <br /> facility according to the equipment manufacturers procedures and limitations and the results as listed <br /> are to my knowledge true and correct.The mechanical/electronic line leak detector test pass/fail is <br /> determined using a low flow rate threshold trip rate of 3 gph at 10psi. <br /> Tester: Jeff Conger Date: 3/5/2014 <br /> Signature: Lic# 1081782 UT rz NACLE <br /> Mechanical/Electronic Leak Detector Test <br />