Laserfiche WebLink
Mechanical Leak Detector Test Data Sheet <br /> ARCO Products Company <br /> Station# 4932 Date 08/04/1999 <br /> Address 16 E.HARDING WAY <br /> STOCKTON,CA.95210 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product PREMIUM PLUS REG UNLEAD <br /> Model CPT CPT CPT <br /> Manufacturer RED JACKET RED JACKET RED JACKET <br /> Full Operating Pressure (psi) 35 35 35 <br /> Line Bleed Back (ml) 600 0 170 <br /> Trip Time (sec) 0.00 0.00 0.00 <br /> Metering Pressure (psi) 10 0 10 <br /> F/E Holding Pressure (psi) 28 0 30 <br /> Test Leak Rate (ml/min) (gph) 189.00 189.00 189.00 <br /> PASS or FAIL PASS FAIL PASS <br /> Replaced All Failed Leak Detectors Yes No N/A Y <br /> If No, Replacement To Be Completed By (Date) <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facililty <br /> according to the equipment manufacturers procedures and limitatios and the results as listed are to my <br /> knowledge true and correct. The mechanical leak detector test pass/fail is determined using a low flow <br /> threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Tanlmology <br /> Technician JEFF CONGER LIC# 90-1116 <br /> Signature <br />