Laserfiche WebLink
Doug Wilson <br />From: Doug Wilson <br />Sent: Thursday, March 18, 1999 2:00 PM <br />To: PAUL FERREIRA (E-mail) <br />Subject: FW: APPROVAL FOR 1771 YOSEMITE AND 16 E HARDING, ENTRY AND INSPECTION <br />-----Original Message ----- <br />From: Doug Wilson <br />Sent: Wednesday, March 17, 1999 2:43 PM <br />To: Bill Merchant (E-mail); PAUL FERREIRA (E-mail) <br />Subject: APPROVAL FOR 1771 YOSEMITE AND 16 E HARDING, ENTRY AND INSPECTION <br />THE ABOVE PLANS ARE APPROVED SUBJECT TO THE FOLLOWING: <br />1 MUST CALL 48 HRS IN ADVANCE <br />2 TANKS MUST NOT HAVE OVER 1% DEFECTION (4 POSITION MEASUREMENT) <br />3 ENGINEER MUST ENTER TANK TO MAKE INSPECTION <br />4 THE EHD CAN REJECT THE TANK FOR CAUSE <br />5 CITY FIRE PERMITS REQUIRED <br />6 INTEGRITY TEST REQUIRED UPON COMPLETION <br />7 CONFINED SPACE ENTRY PERMIT REQUIRED TO BE ON SITE. <br />8 MAP TO HOSPITAL MUST BE PART OF SAFETY PLAN. <br />9 NOTE A MONITORING WELL WILL BE REQUIRED IF TANK IS FOUND TO BE STRUCTURALLY SOUND AND <br />IS TO REMAIN, (IF CONTAMINATION IS FOUND ANYWHERE ON SITE). <br />10 PIPING MAY BE REJECTED BY EHD IF OBVIOUSLY NOT STRUCTURALLY SOUND IE STEEL PIPE ETC. <br />11 MUST PROVIDE INFO ON LAB AND SAMPLER IN ADVANCE FOR APPROVAL.. <br />