Laserfiche WebLink
02-18-1999 O8:54PM FROM 10 14252518782 P.11 <br />Pf in9 (cross-sectional diagram, including connections to tank and dispensers). <br />(A) V r and tbnk riser priiar-Y containment sysrca equipped with overfill prever,rian system that: <br />Restricts delivery of flus+ to tank (Section 2635 (b) (2) (B) or (C)3, or <br />Provide positive shut off of flow to rhe tank at no more than 95 % [section Z635 (b)(Z)(C)j, or <br />(B) Vapor recovery piping designed so it cannot contain liquid phase product, or <br />(C) Suction piping (below grade piping operates at less than atmospheric pressure) lSectian 2636 (a) (3)] <br />' Sloped so contents of the pipe will drain back into the storage tank if the suction is <br />released. <br />No valves or pumps installed below grade_ <br />Inspection method provided to demonstrate cowipliance with section 2636 (a) (3). <br />(0) CPrrodible underground piping protected against corrosion (Section 2636 (b)). <br />(E) I ui�dergroud primary piping will meet all of the following requirements <br />Primary piping in contact with hazardous stbstance under norma( operation conditions shalt be: <br />installed inside a secondary containment system in the form of:.Zsecondary pipe�Vautr or <br />` / _tined trench to be sloped to a collection sump at the tow point of the piping. <br />J/ Primary piping and secondary containment systems will be installed in accordance with industry <br />code of practice and voluntary consensus standards.. <br />Lined trench used as secondary containment <br />Material compatible with the suEstance stored - <br />Covered and capable of supporting any expected vehicular traffic- <br />(F)uriergrou�d piping with secondary containment will be equipped and mtionitared as follows: <br />�I IK secondary containment will be equipped with a continuous monitoring system connected to an audible <br />and visual alarm system - <br />Automatic tine Leak derecrors will be installed on pressurized piping <br />'v LPe <br />Manufacturer: Oalk!,T Model: <br />+ � 3 Li��(r`cccTi2z;v�C <br />Annual monitoring will be conducted on the pressurized piping with secondary containment. <br />Annual line tightness rest will not be required if the continuous monitor shuts down the pump and <br />activates the alarm system when a release is detected and when the continuous monitoring system <br />i <br />i fails or is disconnected. <br />' <br />State Water Resources Control Board "Facility (A)" and "Tank Permit (B)" application forms submitted. <br />plan review and operating permit fees paid. <br />wtat is the approximate depth to ground water. �= rT y t/ AO�) ��<ST�rC/%� i�%�i/9) <br />(t ric Lode source of information - borehole tugs, monitoring well data, water <br />studies, etC.) <br />7 tat number of tanks on site after installation: <br />yC C ty/Cicy Fire District and Building Department notified. <br />19 the event contamination is observed, confirmed or suspected as a result of a leaking UST system it is your <br />rgqsponsibitity lin accordance with (CC2) Title 23, Division 3, Chapter ib, Article 11, Corrective Action <br />Rdquiremebts] as an owner or operator to submit a workplan to PHS -£HO Site Mitigation Unit prior to initiating any <br />assessment.or remediation activities. For further assistance contact the Site mitigation unit at (249) 469-3450. <br />(TIONS OF'AP <br />o .e f'or aarorr must acknowte�dge this responsibility for workptan submittal by signature and datte- below- <br />nate/'�(✓�!, <br />S . 1 Irl i2L "Z' .�- <br />