Laserfiche WebLink
08/05/1999 11:04 2033651543 TANKNOLOGY Fa E 1 <br /> Mechanical Leak Detector Test Data Sheet <br /> ARCO Products Company <br /> Station # 4,01 Date 08/04/1999 <br /> Address 16 E HAR[)INC WA) <br /> STOCKTO N C'd 021A) <br /> Test Information <br /> 1 2 3 4 5 <br /> Product PREMIUM PLUS RFS UNLEAD <br /> Model CPT CPT CPT <br /> Manufacturer REG JACKET RED JACKET REL)JACKET <br /> Full Operating Pressure (psi) 3s 35 3s <br /> Line Bleed Back (ml) 6M o 170 <br /> Trip Time (sec) 0 on 0,00 0 W <br /> Metering Pressure (psi) 10 u to <br /> F/E Holding Pressure (psi) 29 0 10 <br /> Test Leak Rate (ml/min) (gph) i89 164.00 18909 <br /> PASS or FAIL PA55 FAIL PA55 <br /> Replaced All Failed Leak Detectors Yes No N/A x <br /> If No, Replacement To Be Completed By (Date) <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facililty <br /> according to the equipment manufacturers procedures and limitation and the results as listed are to my <br /> knowledge true and correct The mechanical leak detector test pass/fail is determined using a low flow <br /> threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By, Contractor Twnknology <br /> Technician IEFFCONGE�R Lic 40-1116 <br /> Signature <br />