Laserfiche WebLink
LINE & LEAK DETECTOR TEST REPORT <br /> SITE: RIVER POINT LANDING <br /> Identify Time Log of Test Procedures VOLUME REMARKS <br /> Each Line (Military) Ambient Temperature psi READING NET <br /> Weather, Etc. BEFORE AFTER BEFORE AFTER CHANGE Conclusions, Repairs,Comments <br /> DIESEL 1200 PRE TEST 60 <br /> 1215 BEGIN TEST 50 ,0350 <br /> 1230 49 50 .0350 .0340 -.0010 <br /> 1245 49 50 .0335 .0330 -.0005 -.0005 <br /> 1250 BLEED BACK 50 0 .0335 .0635 .0300 <br /> 87 1201 PRE TEST 60 <br /> 1216 BEGIN TEST 50 .0350 <br /> 1231 49 50 .0340 .0335 -.0005 <br /> 1246 50 50 .0330 .0330 .0000 -.0005 <br /> 1251 BEGIN TEST 50 0 .0635 .0990 .0345 <br /> Page 2 of 2 <br />