From: 09/28/2017 13:29 #843 P.003/008 <br /> Monitoring System Certification <br /> 0 <br /> D. Results of Testing/Servicing ED <br /> SEP 2 S 2017 <br /> Software Version Installed: 134.00 <br /> �_i -,4LTH <br /> Com tete the followins checklist: <br /> ® Yes ❑ No* Is the audible alarm operational? <br /> ® Yes ❑ No* Is the visual alarm operational? j <br /> ® Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> ® Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ElYes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) I <br /> ® N/A operational? pt <br /> ® Yes ❑ No* For pressurized piping systems,does the turbine automatically shut down if the piping secondary containment ' <br /> ❑ N/A monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate <br /> positive shut-down? (Check all that apply) ®Sump/Trench Sensors; ®Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks—and sensor failure/disconnection? ®Yes; ❑No. <br /> ® Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no <br /> ❑ N/A mechanical overfill prevention valve is installed),is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 90% <br /> ❑ Yes* ® No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> ❑ Yes* N No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; ❑Water. If yes,describe causes in Section E,below. <br /> ® Yes I ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> ® Yes I ❑ No* Is all monitoring equipment operational per manufacturer's specifications? <br /> *In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: <br /> Tank 1 Diesel STP Sump Annular sensor- _ <br /> Tank 2 Diesel STP Sump Anamarmsor-07894380-304 <br /> FM Sump Annular sensor–u-78943W-3U4 <br /> Tank 3 Bledlese!STr Sump Annular sensor-1115y4JOU-JU4 <br /> Fill Sump Al D--304 <br /> Vent Sump Annular sensor–0 789438"04 <br /> Dispensers Annular Sensors for: 1;615; 1129-512;413;zt; 7 with sensor model.078 9435-0-JUR <br /> Transition Piping Sump Sensor–0 7894380 208 <br /> Transition Piping Sump Annular–07894380-304 <br /> Page 2 of 4 <br /> i <br /> UN-036-2/4 wvl,.unidocs.org Rev.01/17/08 <br />