Test Date: 1210312002 <br /> nkrockpgy <br /> Work Order: 2224678 <br /> SUMP TESTS <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> " <br /> Type Tank orDisp Manufacturer Model or Diam./Width/Length Depth Test Method Start Initial Level Finish Final Pass/ <br /> # Material I"} ("} Time Level Change Time Result Fait <br /> STP Sump REGULAR Smith Fiberglass 48" 66" Hydrostatic-VPLT 0826 17" 0-00011 0857 0.001 Pass <br /> STP Sump SUPREME Smith Fiberglass 48" 661" Hydrostatic-VPLT 0826 17" 0.00032 0857 0.005 Pass <br /> STP Sump DIESEL Smith Fiberglass 48" 661" Hydrostatic-VPLT 0921 17" 0.00163 0952 0.025 Pass <br /> Dispenser Pan 112 Bravo Metal 181' 9" Hydrostatic-VPLT 1014 3" 0.00023 1030 0.005 Pass <br /> Dispenser Pan 314 Bravo Metal 18'" 9" Hydrostatic-VPLT 1014 3" 0.00008 1030 0.002 Pass <br /> Dispenser Pan 516 Bravo Metal 181' 91" Hydrostatic-VPLT 0928 3" 0.00014 0944 0.003 Pass <br /> Dispenser Pan 718 Bravo Metal 18" 9" Hydroslalic-VPLT 0909 3" 0.00005 0925 0.001 Pass <br /> Comments: <br />