Laserfiche WebLink
ITISIntegrity Tank Testing Systems, Inc. <br /> f,1RY (I <br /> .ENVIRONMENTAL HEALTH <br /> PERMIT/SERVICEs <br /> TEST DATA AND <br /> TEST RESULTS <br /> April 12, 1988 <br /> Mr. James Anagnos <br /> Sun West Grocery & Liquors <br /> 801 East Hwy 12 <br /> Lodi, California <br /> Dear Mr. Anagnos: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than .02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TA;JK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOC_1TION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 10, 000 Sup U/L Gas -. 0333 Yes <br /> Center 10, 000 U/L Gas -. 03004 Yes <br /> West 10, 000 Reg Gas -.D3194 Yes <br /> Please contact us if you need additional assistance or <br /> Information. <br /> Sincerely , <br /> W. Savage <br /> Certified Tester <br /> 800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />