Laserfiche WebLink
PUBLIt HEALTH SES\ �//]�� <br /> + � � i C E S P.4...N <br /> SAN JOAQUIN COUNTY <br /> ENVIRONMENTAL HEALTH DIVISION q :� <br /> Ernest M. Fujimoto, M.D., M.P.H., Acting Health Officer <br /> 445 N. San Joaquin Street • P. O. Box 388 • Stockton, CA 95201-0388 c'�iFoaN P <br /> 209/468-3420 <br /> Date 6/14/95 <br /> LEX COFFROTand ASSOCIATES 2115 J Streee t, Suite 213COPY Sacramento, CA 95816 <br /> RE: Proposed installation of underground storage tanks at 140 <br /> Lathrop Road, Lathrop. <br /> 1. The overspill containment system planned to be used does <br /> not indicate volume on cutsheet. The containment system <br /> must have a minimum volume of five gallons. Provide <br /> information. <br /> 2 . The plans do not indicate the use of an overfill <br /> protection device. Provide information on overfill <br /> protection. <br /> 3 . Piping must undergo tightness test, by a state approved <br /> method, prior to final approval of installation. <br /> 4 . Inorder to be in compliance with the 1998 upgrade <br /> requirments the tank system must be equipted with the <br /> following: <br /> a. Electronic shutoff of turbin if leak is detected, <br /> probe malfunctions or is disconnected. <br /> b. Overspill protection. <br /> c. Overfill protection. <br /> d. striker plates. <br /> Ernest M. Fujimoto, M.D. , M.P.H. <br /> Acting Health Officer <br /> Robert McClellon R.E.H. S. <br /> Environmental Health Division <br /> A Division of San Joaquin County Health Care Services <br />