0 <br />Mechanical 1 Electronic Leak Detector Test <br />Site: <br />Lathrop Chevron <br />140 E Lathrop Rd. <br />Lathrop, Ca. 95330 <br />Test Information <br />Test Company <br />Pinnacle Fuel Compliance <br />P.O. Box 32849 <br />San Jose, CA 95152 <br />(408)206-9840 <br />1 <br />2 3 <br />4 <br />Product Regular <br />Supreme Diesel <br />Manufacturer VMI <br />VMI VMI <br />Model LD2000 <br />LD2000 LD2000 <br />Full Operating Pressure (psi) 29 <br />28 28 <br />Line Bleed Back (ml) 130 <br />130 155 <br />Trip Time (sec) 4 <br />3 4 <br />Metering Pressure 18 <br />17 18 <br />FIE Holding Pressure (psi) 22 <br />21 22 <br />Test Leak Rate (ml/min)(gph) 189 <br />189 189 <br />PASS or FAIL PASS <br />PASS PASS <br />This form certifies that the annual line leak detector tests were performed at the above referenced facility <br />according to the equipment manufacturers procedures and limitations and the results as listed are to my <br />knowledge true and correct.The mechanical/electronic line leak detector test pass/fail is determined using a low <br />flow rate threshold trip rate of 3 gph at 10psi. <br />Tester: Jeff Conger <br />Date: 12/16/2013 <br />Signature: Lic# 10817$2 -UT <br />Mechanical/Electronic Leak Detector Test <br />0 <br />'UN <br />PINNACLE <br />