Laserfiche WebLink
MONITORING SYSTEM CERTIAEA OIT N <br />CERTIFICATION/ TEST DATE: Janus 14, 2014 JAN 21 2014 <br />Al. FACILITY A2. OWNER <br />Name Tower Mart # 104 Name Tower Energy Group, Inc ENVIRONMENTAL HEF': I <br />Address 192 Lathrop Road, Lathrop, CA 95330 Address 1983 West 190th Street, Torrance €*Akbof <br />djRVICE:i <br />Phone # 209-858-4998 Phone # 916-285-7402 ext 10o <br />Contact Desiz Burns Contact Mark Vasev <br />ID. RESULTS OF TESTING / SERVICING <br />Make / Model of Monitoring System: Veeder-Root TLS -350 <br />Software Version Installed: 327.04 <br />Complete the following checklist: <br />SN# 80548678305001 <br />■ Yes <br />❑ No* <br />Is the audible alarm operational? <br />■ Yes <br />❑ No ` <br />Is the visual alarm operational? <br />_ ■ Yes <br />❑ No • <br />were all sensors visually Inspected, functionally tested, and contimled operneonal? <br />■ Yes <br />❑ No * <br />Were all sensors installed at lowest point of secondary containment and positioned so that other equipment <br />will not interfere with their proper operation? <br />❑ Yes <br />❑ No* <br />If alarms are relayed to a remote monitoring station, Is all communications equipment (e.g. modems) <br />_ <br />■ N/A <br />operational? <br />0 Yes <br />❑ No* <br />For pressurized piping systems, does the turbine automatlully shut down If the piping secondary containment <br />❑ N/A <br />monitoring system detects a leak, falls !o operate, or is electricalty dbconnected7 If yes: which sensors InWate <br />positive shutdown? (check all that apply) ■ SumpRrench sensors; ■Dispenser Containment Sensors. <br />■ Yes <br />❑ No • <br />Did you confirm positive shutdown due to leaks and sensor failure/diseonnection? <br />❑ as <br />❑ No* <br />For tank systems that utilize the monhodng system as the primary tank oveMlll warning device (I.e. no <br />■ N/A <br />mechanical overnll prevention valve b installed), is the overfill warning alarm visible and audible at the tank <br />_ <br />011 polnt(s) and operetlng properly? If so, at what percent of tank capacity does the alarm trigger? <br />■ Yes " <br />❑ No <br />_ <br />Was arty monitoring equipment replaced? If yes, Idant Hy specific sensors, probes, or other equipment replaced <br />and Iist the manufacturer name and model for all replacement parts in Section E, below. <br />■ Yes ` <br />❑ No <br />Was any liquid found Inside any secondary containment systems designed as dry systems? <br />(Check all that apply) ❑ Product; ■ Water. If yes, describe causes In Section E, below. <br />■_ Ye�ONo*� <br />Was monitoring system set-up reviewed to Insure proper settings? Attach set-up reports, if applicable. <br />■ .YeIs <br />all monitoring equipment operational per manufacturer's specifications? <br />In Section E below, describe how and when these deficiencies were or will be corrected. <br />t, UUMMENTS <br />Replaced 91 STP sump sensor. <br />Removed liquid from diesel STP sump. <br />Replaced keyboard, causing a Warm start loop. Monitor had to be cold -started before certification. <br />Page 2 of 3 <br />