Laserfiche WebLink
ITTSIntegrity T¢nt TestingSpgtems, inc. , <br /> wCFlIIV <br /> DEC 19 1988 TEST DATA AND <br /> %CZ7 ,,.. R <br /> �F! ,"•-' ._. ''CST RESULTS <br /> !'RFCAN <br /> SkV{.'Vf:S9 rLCJA%J <br /> December 19 , 1988 <br /> P99 <br /> American Savings & Loan VC9 <br /> P . 0 . Drawer D FEB <br /> Stockton, California � � 1y� <br /> Mr . Richard Robbins : PEAIWIrjSERviCES�j <br /> Following is a summary of the precision testing we recently <br /> conducted on your, underground storage tank (s) . <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate governmental <br /> agency . <br /> A tangy: system is considered tight , according to the current <br /> rules , if the loss or gain is less than . 05 gallons per one hour <br /> of testing . If the results are beyond these parameters , you <br /> should consider taking some remedial action . <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> N/E Of Off . <br /> Middle Tnk 12 , 000 U/L Gaso . . 036 Yes <br /> S/E Of Off . <br /> South Tnk 10, 000 U/L Gaso . - . 018 Yes <br /> S/"v of Off 10, 000 U/L Gaso . ( - . 053 No <br /> Please contact us if you need additional assistance or <br /> information . <br /> Sincerely, <br /> 4ae <br /> W. N . Salvage <br /> Certified Tester <br /> ?$ 166 F mk wad cirde, 9WCftM CA"206 (209466-8036 <br />