Laserfiche WebLink
CERTIFICATE (+TESTING UNDERGROUND STOI*E TANK SYSTEMS <br /> Pro Tank, Inc. <br /> 3545 Lomita Blvd., Suite G <br /> Torrance, CA 90505-5022 <br /> (310) 891-0470 <br /> Client: USA PETROLEUM, INC. Site: USA STATION #065 <br /> 1261 East 9th Street 2500 W. Lodi <br /> Pomona, CA 91768 Lodi, CA 95242 <br /> 909-622-3424 209-333-9834 <br /> The following tests were conducted at the site described above in accordance with all applicable portions of Federal, NFPA, and Local regulations. <br /> TANK SYSTEM INFORMATION <br /> Type Type <br /> Tank Tank Product Tank Stage Stage 11 <br /> Capacity Diameter Level Total Construction/ Vapor Vapor <br /> Tank in In in Gallons Percent Tank Recovery Recovery <br /> Number Gallons Product Inches Inches Filled Filled Material Present Present <br /> T1 12K 89 11891 Unload 89 95 89 11576 97% SW Steel Dual Balance <br /> T2 12K 87 11891 Unload 87 95 74.5 10004 84% SW Steel Dual Balance <br /> T3 12K 92 11891 Super 92 95 78 10443 1 88% SW Steel Dual Balance <br /> TESTING RESULTS <br /> Wetted <br /> Portion Vent Lines Leak Leak <br /> VPLT of Ullage and/or Product Detector Detector <br /> Tank Leak Rate Tank Test Vapor Lines Lines Present] Results <br /> Test Date Number (gph) PASS/FAIL PASS/FAIL PASS/FAIL PASS/FAIL Yes/No PASS/FAIL <br /> 04-30-96 T1 12K 89 -0.030 PASS PASS PASS PASS Yes PASS <br /> 04-30-96 T2 12K 87 -0.035 PASS PASS PASS PASS Yes PASS <br /> 05-01-96 <br /> 06-27-96 <br /> 04-30-96 T3 12K 92 -0.048 PASS PASS PASS PASS Yes PASS <br /> 05-01-96 <br /> ProTank, Inc. Customer Service Representative Testing Conducted by <br /> Daisy E. Mosby Rosendo R. Robles <br /> Technician Certification No: 99-1593 <br /> Pro Tank, Inc. - 3545 Lomita Blvd, Suite G - Torrance, CA 90505- (310) 891-0470 <br />