Laserfiche WebLink
• TRI—TECH • <br /> Tank Testing, Inc. <br /> HYDROSTATIC LINE TEST REPORT <br /> TEST LOCATION. . = USA #65 TEST DATE. . . . . = 04/03/91 <br /> 2500 W. Lodi CONTACT. . . . . . . = Ken Green <br /> Lodi , Ca. PHONE. . . . . . . . . = 714-622-3424 <br /> TECHNICIAN. . . . . = Richard Rogers PRODUCT LINES = PASS <br /> LICENSE # . . . . . . = 90-1197 LEAK DETECTORS = OPERATIONAL <br /> EXPIRATION DATE = 12/31/93 <br /> TEST CALCULATIONS <br /> The maximum allowable indicated leak rate under NFPA requirements can be no <br /> greater than -. 01 GPH. <br /> Gal . Loss = Lines Loss x . 0003 Gal . <br /> GPH Loss = Gal . Loss per 15 minute test x 4 <br /> PRODUCq21 :45 <br /> ME PSI LEVEL LEVEL LINES GAL. GPH RESULT <br /> START END LOSS LOSS LOSS <br /> Super 50 63. 7 63. 2 -05 - . 0015 - .0060 Pass <br /> Super 22 :00 50 63.0 62. 7 -03 - . 0009 - .0036 Pass <br /> PRODUCT TIME PSI LEVEL LEVEL LINES GAL. GPH RESULT <br /> START END LOSS LOSS LOSS <br /> Unleaded 21 :45 50 56 . 8 55 . 9 -09 - . 0027 - .0108 Pass <br /> Unleaded 22 :00 50 55 . 5 54. 9 -06 - .0018 -. 0072 Pass <br /> PRODUCT TIME PSI LEVEL LEVEL LINES GAL. GPH RESULT <br /> START END LOSS LOSS LOSS <br /> Regular 21 :45 50 41 . 2 40 . 9 -03 -.0009 - .0036 Pass <br /> Regular 22:00 50 40. 9 40. 6 -03 -. 0009 - . 0036 Pass <br />