PRECISION TANK TESTING, INC. <br /> P <br /> March 22 , 1990 <br /> Ken Green RE: USA #65 <br /> USA Petroleum 2500 W. Lodi <br /> 1261 E. 9th Street Lodi , Ca. <br /> Pomona , CA. 91766 <br /> PTT REF. #: USA65-70-900313 <br /> Dear Mr. Green, <br /> Enclosed are the results of the tank integrity tests performed at 'the <br /> above location on March 13, 1990. The system used for the tests is <br /> the Horner "Ezy-Chek" Tank Testing System. This system meets NFPA <br /> requirements , and is able to detect a leak rete of . 05 gallons per <br /> hour. <br /> The criterion of . 05 gallons per hour is not to be construed as a <br /> permissable leak rate. Rather, it is an' accuracy tolerance and allows <br /> for the many variables involved. <br /> We assume no responsibility for product leakage . Our responsibility <br /> extends only to testing of the tank as tight or not tight as of the <br /> date tested, within the accuracy tolerance of the Horner Test System. <br /> TANK DATA II <br /> TEST DATA <br /> ----------- ----------------------- <br /> TANK TANK PUMP 11 TEST PROD. LEAK LEAK <br /> NO. CAP . PROD. MAT. TYPE ii LEVEL TANK LINE DET. RATE <br /> 1 12K Sup Stl Tokheim I ; 97 Tight Tight Good -. 0250 <br /> 2 12K Unl Stl .Tokheim ; I 98 Tight Tight Good - .0149 <br /> 3 12K Reg Stl Tokheim { { _ 97 Tiaht Tight Good -. 0220 <br /> Thank you for the opportunity to work with you in meeting your tank <br /> testing needs . <br /> Very truly yours , <br /> Doug Rowlands <br /> 3960 LAUREL CANYON BLVD., SUITE 422 e STUDIO CITY, CA 91604 • 818-766-2002 • 818-766-TANK FAX 818-766-8263 <br />