Laserfiche WebLink
Test Date: 04-11-95 (USA #OF� • PO#: KG 73580 <br /> TANK TESTING DATA <br /> =#- <br /> E VPLTNPLT-A <br /> T1 T2 T3 <br /> UNL 89 UNL 87 UNL 92 <br /> ): 11,891 11,891 11,891 <br /> Siphoned Tanks: NO NO NO NO <br /> Manifolded Piping: NO NO NO NO <br /> Remote Fills: NO NO NO NO <br /> Tank Diameter (inches): 95 95 95 <br /> Tank Bottom to grade (Inches): 122 122 125 <br /> Tank Bottom to fill Top (Inches) 122 122 125 <br /> Fill Pipe Length (Inches); 28 28 28 <br /> Fill Pipe Diameter (Inches); 4 4 4 <br /> Fluid Level (Inches); 62 66 62 <br /> Fluid Volume (Gallons): 8295 8898 8295 <br /> Percentage of Capacity filled (%) 69 74 69 <br /> Water in tank (Inches): 1.0 1.0 0 0 <br /> Specific Gravity: 0.750 0.750 0.750 0.750 <br /> Thermal coefficient of Expansion (°F): 0.00064 0.00064 0.00064 0.00064 <br /> Rate of Temperature Change (°F/Hr): -.02 -.005 -.02 <br /> 611nder Underfill Test: UNDERFILL UNDERFILL UNDERFILL UNDERFILL <br /> thermistors: 5 5 5 5 <br /> Groundwater (Feet below BELOW BELOW BELOW BELOW <br /> tank): TANK TANK TANK TANK <br /> ermined: Temperature Temperature Temperature Temperature <br /> variation in variation in variation in variation in <br /> backfill backfill backfill backfill <br /> ation (Hr:Mn:) 2:44 3:073:03 2:00 <br /> (GPH►: - 049 -.029 + .047 <br /> PASS PASS PASS PASS <br /> Tank Test Comments: None. <br /> ProTank, Inc. - 3545 Lomita Blvd, Suite G -Torrance, CA 90505 - (310) 3891-0470 <br />