Laserfiche WebLink
Test Date: 04-11-95 (USA #0Q1 • PO#: KG 73580 <br /> LINE TEST DATA <br /> Line Test Method Used: Proline Test Series Ill, Version 1.0 <br /> Tank Number: T1 T2 T3 <br /> Product: UNL 89 UNL 87 UNL 92 <br /> Pump type: TURBINE TURBINE TURBINE <br /> Pump Make: A. 0 . SMITH A. O. SMITH A.O. SMITH <br /> Isolator: SILVER SILVER SILVER <br /> BULLET BULLET BULLET <br /> Line Material: STEEL STEEL STEEL <br /> Line Diameter (In): 2 2 2 <br /> Test Pressure (Psi): 50 50 50 <br /> Test Time (Min.): 15 15 15 <br /> Finish Pressure (PSI: 36 36 32 <br /> Volume change (MI): 12 38 12 <br /> Volume change (GPH): 0.013 0.040 0.014 <br /> Pass/Fail PASS PASS PASS <br /> Line Test Comments: <br /> LEAK DETECTOR DATA <br /> Test Method used: Red Jacket Approved AVO <br /> Tank Number: T1 T2 T3 <br /> Product: UNL 89 UNL 87 UNL 92 <br /> Manufacturer: RED JACKET RED JACKET RED JACKET <br /> Leak Detector Model: XLD(116-035) XLD (116036) XLD (116047) <br /> Serial Number: 304916171 20994-2432 022495 <br /> Pass/Fail: PASS PASS PASS <br /> FLeak Detector Comments: REPLACE LEAK DETECTORS FOR TANKS #1 UNL 89 AND #3 UNL <br /> 92 <br /> oTan nc. - 5 omrta &v ., uite - Torrance, 511�(3i <br />