Laserfiche WebLink
Tracer Research Corporation <br /> CER771__ ICATION_ <br /> Job Number : 0101061 <br /> Location: USA Petroleum #65 Date : 04/23/92 <br /> 2500 West Lodi <br /> Lodi, CA <br /> TANK# PROMQT SI (ga h TRACER LEAK STATUS <br /> Tank 1 Plus 12,000 FB Pass <br /> Tank 2 Unleaded 12,000 DA. Pass <br /> Tank 3 Premium 12,000 FB Pass <br /> Tracer Research Corporation certifies that the tanks listed in the above table have <br /> been tested by means of Tracer Tight@, which meets the criteria set forth in NFPA 329 for <br /> a precision leak test. According to EPA standard test procedures for evaluating leak <br /> detection methods, the Tracer Tight@ method is capable of detecting leaks of 0.05 gallons <br /> per hour with a Probability of Detection (PD) of 0.97 and Probability of False Alai-in <br /> (P17A) of 0.029. <br /> Submitted by: _ <br /> Jim Cook <br /> Tracer Rthearch Corporation <br /> Testers State License Number: 95-1502 <br /> The following criteria are used for the classification of leakage based on the presence or <br /> absence of tracer. <br /> PASS EAI1, <br /> Criteria: Criteria: <br /> No tracer detected tracer detected <br /> - 3 - <br />