r , <br /> CONFIDENCE UST SERVICES, INC. 417 MONTCLAIR STREET <br /> BAKERSFIELD, CA 93309 <br /> (805) 631--3870 <br /> RES - SYSTEM II <br /> PRECISION TANK & LINE TEST RESULTS SUMMARY <br /> Invoice Address : Tank Locations W. O. #: 1578 <br /> IEL BOKIDES PERTOLLUM MBP EXXON I. D. Number: N/A <br /> 091 NAVY DRIVE 501 WEST L._ODI AVE. Technician :D. YOUNG <br /> !TOCKTON, CA 95206 LODI, CA Tech. 0:86116 Van#:01 <br /> Dates 09-01-94 Time Start : 06 :00 End : 1.0 :00 County : S.J <br /> Facility Phone#: ( ;209) 94;-2011 Groundwater Depth : 1.44"+ Blue Prints : NO-) <br /> Contact : NICK 8d.1KIbhS' Date ;Time system was filled : 6+ HOUR_; <br /> Tank Fill/Vent Product Type Of Vapor Inches of Pump Tank <br /> Tank Capacity Product Tank Vapor Lines Line Recovery Water/Tank Type Material <br /> 1 10000 PLUS PASS PASS PASS II 0.00" TURB. SWS <br /> 2 10000 REGULAR PASS PASS PASS II 0. 00" TURB. SWS <br /> 3 10000 SUPREME PASS PASS PASS II 0.00" TURB. SWS <br /> 4 <br /> 6 <br /> 6 <br /> Additional Information : TEST TECHNICIAN: DOUG YOUNG O. T. T. L. #90--1.076 <br /> qLL MECHANICAL LINE. LEEK. DFTEL ORS WERE TESTED AND ARE OPERATIONAL. <br /> SITE LOG TIME <br /> Set Up Equip: 06 :00 <br /> Bled Product Lines : YES <br /> Bled Vapor Lines : YEI <br /> Bled Vent lines : YI:_S <br /> Bled Turbine : YES <br /> Bled Suction Pump: N/0 <br /> Risers Installed : YES <br /> a) This system and method meets or exceeds the criteria in USEPA 40CFR <br /> part 280, NFPA 329-87 and all applicable state and local codes. <br /> b) Any failure listed above may require further action, check with <br /> all regulatory agencies. <br /> Copyright (c) 1989 by RES, Inc. p <br /> Certified Technician Signature *, -5 <br /> /� Date � `� / <br />