Laserfiche WebLink
Integrity Tank Testing Systems, Inc. <br /> 'LEST DATA AND <br /> TEST RESULTS <br /> t15 August 10, 1987 <br /> 1 f997 . <br /> Mr. Ed Rocha EHFER -M NTAL HEALTH <br /> Ed Rocha Livestock SERVICES <br /> 2973 Loomis Road <br /> Stocktbn , CA 95295 <br /> Dear Ed : <br /> Following is a summary of the precision testing we recently <br /> r.-nducted on your underground storage tank(s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rat-d for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than .02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action . <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 12 , 000 Diesel Fuel -. 01595 Yes <br /> South 8,000 Diesel Fuel <br /> manifolded <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> � P ank Keser <br /> Certified T ter <br /> -W 26966 eS <br /> oc on, (2 466-803 <br />