Laserfiche WebLink
Quality Petroleum Equipment <br />LDT - 890 Test Form <br />Test Information <br />Date: 4121/2014 Test Company: Mid Valley Consulting & General 9pg. <br />Telephone: 530-749-9892 Contact: James Day <br />Site ID FAST AND EASY Address: 10878 N. HWY 99 <br />City: STOCTON State: CA, <br />Type of Test Equipment: VMI LOT - 890kAF <br />Submersible Pump Identification <br />MFG: RED JACKET Model No: P15S1 Serial No: 1722 <br />Leak Detector Identification <br />MFG: RED JACKET Model No: FXID Serial No: 9532 <br />Replacement Leak Detector Identification <br />MFG Model No: Serial No <br />Line Conditions <br />1. Type of Pipe: FRP 2. Diameter of Pipe: 2" 3. Length of Pipe 601 <br />4. Burial Depth of Leak Detector: 24" 5. Kind of Fuel: DIESEL 6. Date of Last Test: 2013 <br />Test Conditions <br />1. Operating Pump Pressure: 29 PSI 2. Gallon per hour test rate:_3 @10 psi <br />3. Static Line Pressure (Pump Off): 16 PSI 4. Bleed back Test (Pump Off): 120 ml <br />5. Step -Through time to full flow 4 seconds (0 psi to full pump pressure, no leak) <br />6. Leak detector stays in Leak Search Position with a 3 GPH leak -Yes: X PASS No: FAIL <br />7. Was the leak detector adjusted - Yes: No: <br />Symptoms <br />1. Won't find 3 GPH leak: 2. Stays in Slow Flow: <br />3. Other: <br />