Quality Petroleum Equipment <br />LST - 890 Test Form <br />Test Information <br />Date: 4/21/2014 Test Company: Mid Valley <br />Consulting & General Eng. <br />Telephone: 530-749-9892 Contact: James Day <br />Site ID FAST AND EASY Address: 10878 N. HWY 99 <br />City: STOCTON State: <br />Type of Test Equipment: VMI LDT - 8901AF <br />Submersible Pump Identification <br />MFG: RED JACKET Model No: P150S1 <br />Serial No: 1061 <br />Leak Detector Identification <br />MFG: RED JACKET Model No: FXIV <br />Serial No: 5381 <br />Replacement Leak Detector Identification <br />MFG Model No: <br />Serial No <br />Line Conditions <br />1. Type of Pipe: FRP 2. Diameter of Pipe: 2" 3. Length of Pipe 80' <br />4. Burial Depth of Leak Detector: 22" S. Kind of Fuel: 91 6. Date of Last Test: 2013 <br />Test Conditions <br />1. Operating Pump Pressure: 28 PSI 2. Gallon per hour test rate - _3 @10 psi <br />3. Static Line Pressure (Pump Off): 14 PSI 4. Bleed back Test (Pump Off): 90 ml <br />5. Step -Through time to full flow 5 seconds (0 psi to full pump pressure, no leak) <br />6. Leak detector stays in Leak Search Position with a 3 GPH leak -Yes: X PASS No: FAIL <br />7. Was the leak detector adjusted - Yes: No: <br />Symptoms <br />1. Won't find 3 GPH leak: 2. Stays in Slow Flow: <br />3. Other: <br />