Laserfiche WebLink
PRECISION <br />INDUSTRIES <br />INC <br />1041 S. PERSHING AVE., STOCKTON, CALIFORNIA 95206 <br />209/462-9911 NO. CALIF. 800/332-5900 <br />CALIFORNIA STATE LIC. 467 293 <br />JULY 29, 1988 <br />LODI AIRPORT <br />23987 N. HIGHWAY 99 <br />ACAMPO, CA 95220 <br />ATTENTION: BOB KUPKA <br />LOCATION: SAME AS ABOVE <br />RESULTS OF TANK TESTS PERFORMED JULY 28 & 29, 1988 <br />TANK #2 - 5,000 gallon aviation gas 80 oct. tank - <br />Full system test indicated a volume change of <br />+.0040 gallons per hour under test conditions. <br />Full system test is within state guidelines. <br />TANK #3 - 4,000 gallon aviation gas 100 oct. tank - <br />Full system test indicated a volume change of <br />+.0079 gallons per hour under test conditions. <br />Full system test is within state guidelines. <br />PRECISION INDUSTRIES, INC. <br />NICK CLAYTON <br />TANK TEST COORDINATOR <br />NC/pw <br />Enc. <br />. MAR 2 01989 <br />ENVP �MMF, SERVICES " <br />