<br /> 1 2 3 4 B 6 7 8 9 10 11 12 13 1q 18 18 n CONDUCTORS AS1REDID 21
<br /> INSULATED BUSHED NIPPLEGENERAL NOTES CADMASM\NOTES\CH\16ELECT\1600NOIC
<br /> FOR CONDUCTOR PROTECTION ON 19930820.,a4yu
<br /> HN
<br /> CONDUIT SEAL(S): CROUSE- 1. ALL ELECTRICAL WORK SHALL BE IN COMPLIANCE WITH MOST RECENT EDIRON OF R
<br /> HINDS CAT, #EYS 26 THE NATIONAL ELECTRICAL CODE AND ALL APPLICABLE STATE AND LOCAL CODES
<br /> (OR EQUAL) AS REQUIRED. AND ORDINANCES.
<br /> HANDHOLE 2. ALL EQUIPMENT, MATERIALS, AND WRING METHODS IN HAZARDOUS AREAS SHALL
<br /> ALVANIZED RIGID STEEL REIN ACCORDANCE WITH N.E.0 ARTICLES 500 THROUGH 514.
<br /> z I I G
<br /> CONDUIT 3 ALL ELECTRICAL MATERIAL SHALL BE NEW AND LISTED WITH THE UNDERWRITERS
<br /> SIGN OR YARD LIGHT COLUMN LABORATORIES INC.. SHALL MEET THEIR REOOIREMENTS. AND SHALL BEAR THEIR
<br /> LABEL WHEREVER STANDARDS HAVE BEEN ESTA13USHED AND LABEL SERVICE 15
<br /> FINISH GRADE LINE REGULARLY FURNISHED BY THAT AGENCY.
<br /> 4, CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT,
<br /> TRANSPORTATION, AND PERFORM ALL OPERATIONS NECESSARY OR INCIDENTAL TO
<br /> PROPER EXECUTION AND COMPLETION OF ALL 'ELECTRICAL WORK' WHETHER
<br /> P
<br /> d #6 AWG BARE COPPER SPECIFICALLY MENTIONED OR NOT. MATERIALS AND EQUIPMENT PROVIDED BY
<br /> SUPPLEMENTARY GROUND IF OWNER WILL BE AS SPECIFICALLY NOTED.
<br /> REQUIRED BY LOCAL CODE
<br /> 12 PVC CONDUIT 5. CONDUCTORS SHALL BE STRANDED COPPER TYPE THHN/THWN, UNLESS OTHER-
<br /> WISE NOTED.
<br /> 6" 6 ELECTRICAL CONTRACTOR TO PULL ELECTRICAL PERMIT.
<br /> MIN. 7. THE CONTRACTOR IS REMINDED THIS PROJECT IS A MODIFICATION AND REMODEL
<br /> TO AN EXISTING FACILITY. EXISTING CIRCUITING HAS NOT BEEN ENTIRELY
<br /> VERIFIED AND THESE DRAWINGS AND SPECIFICATIONS MUST BE ACCEPTED NTH
<br /> THIS UNDERSTANDING.
<br /> PVC TO METAL CONDUIT
<br /> N COUPLER (TYP) 8. SEE MECHANICAL PLANS FOR EXACT LOCATION OF, AND LOADS REQUIRED FOR, N
<br /> ANY NEW H.V.A,C EOUIIPMENT.
<br /> H16YARD LIGHT/SIGN CONDurr 9, ALL NEW SIGNS AND SPANNERS MUST HAVE SHUT OFF CAPABILITIES AT THEIR
<br /> RESPECTIVE LOCATIONS. WHERE A SIGN OR SPANNER IS SERVED BY MORE THAN
<br /> ONE CIRCUIT, THE CIRCUIT BREAKERS SHALL BE MECHANICALLY INTERLOCKED BY
<br /> NO SCALE LI DTLS\CEN\I6ELECT\tl OCOND\16110046 19930805.15}Iy0 MEANS OF HANDLE TIES.
<br /> DISP. ??. CUIRCUIT BREAKERS USED AS MOTOR DISCONNECTION MEANS PER N E.C. 430-102(6)
<br /> SHALL BE CAPABLE OF BEING LOCKED IN THE OPEN POSITION.
<br /> DI SP 10. ELECTRICAL DRAWNGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE
<br /> AND LOCATION OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, ALL
<br /> DIMENSIONS AND CONDUIT/CONDUCTOR DATA SHALL BE VERIFIED IN THE FIELD,
<br /> M
<br /> PLAN CONDUIT OPENING (TYP.) 11. ELECTRICAL CONTRACTOR SHALL PERFORM ALL CUTTING AND PATCHING OF
<br /> WALLS, CEILINGS, FLOORS, ETC., FOR INSTALLATION OF ELECTRICAL/OATA BOXES.
<br /> CONCEALED CONDUIT, ETC. ALL PATCHING SHALL MATCH SURROUNDING MATERIAL
<br /> LOCATE PER MANUFACTURER'S AND FINISH.
<br /> SPECIFICATIONS 12, THE OWNER RESERVES THE RICHT TO RELOCATE ALL UGHTING, OUTLETS, SWITCHES.
<br /> AND TELEPHONE OUTLETS, BEFORE THEY ARE ROUGHED IN, AT NO EXTRA COST.
<br /> JUNCTION BOX (TYP.) 13. ALL SWITCH PLATES IN OCCUPIED AREAS SHALL BE STAINLESS STEEL, SWITCHES
<br /> 3/4" UNION CROUSE HINDS AND RECEPTACLES SHALL BE IVORY. DEDICATED ISOLATED GROUND CIRCUIT
<br /> J CAT #UNY 205 OR EQUAL RECEPTACLES SHALL BE ORANGE.
<br /> (TYP.) 14. FOR ALL EXISTING LIGHT FIXTURES (INTERIOR, EXTERIOR, SHOP, CANOPY, SOFFIT,
<br /> YARD, ETC.) THAT
<br /> ARE TO REMAIN, CONTRACTOR SHALL RELAMP FIXTURES NTH L
<br /> I" NEW LAMPS, CLEAN FIXTURES, REPLACE BROKEN OR DISCOLORED LENSES,
<br /> ELEVATION LOCATE PER MANUFACTURER'S REPLACE DEFECTIVE BALLASTS, WIRING, AND STARTING EQUIPMENT, AND VERIFY
<br /> SPECIFICATIONS THAT ALL FIXTURES ARE IN PROPER OPERATING ORDER.
<br /> 3/4' SEAL FITTING 15. ELECTRICAL CONTRACTOR TO VERIFY EXISTING GROUNDING SYSTEM 15 CONNECTED
<br /> CROUSE HINDS CAT #EYS 26 AND FUNCTIONING PROPERLY. ALL EQUIPMENT SHALL BE GROUNDED IN ACCOR-
<br /> OR EQUAL (TYP ) DANCE WITH N.E.C, ARTICLES 250 AND 501-16. ALL CONDUIT SHALL HAVE AN
<br /> EQUIPMENT GROUNDING CONDUCTOR. THE GROUNDING CONDUCTOR SHALL BE
<br /> NOTES: BONDED TO THE METAL FRAMES OF ALL FIXED ELECTRICAL EQUIPMENT.
<br /> 1. VERIFY MANUFACTURER'S DISPENSER DIMENSIONS. MODEL, AND JUNCTION BOX 16. CONDUIT ROUTING SUGGESTED ONLY. ALL INTERIOR BUILDING CONDUIT SHALL BE
<br /> LOCATIONS PRIOR TO STUBBING CONDUITS, A MINIMUM 1/2" EMT UNLESS NOTED OTHERNASE. ALL CONDUIT IN SALES AREA
<br /> SHALL BE INSTALLED CONCEALED IN WALLS, FLOORS, OR CEILINGS. WHERE
<br /> 2. VERIFY ORIENTATION OF DISPENSERS PRIOR TO STUBBING CONDUITS. CONCEALED CONDUIT IS IMPRACTICAL WIRING SHALL BE IN WIREMOLD. PAINTED K,
<br /> TO MATCH THE SURROUNDINGS.
<br /> K16DISPENSER CONDUIT 17. ALL EMPTY CONDUITS SHALL BE EQUIPPED WITH 3/16" POLYPROPYLENE PULL
<br /> LINES. CAP ALL EMPTY CONDUITS.
<br /> NO SCALE I DTL5\GEN\I6ELECT\I1000ND\IBA006G 19930804173056 18 WHEN IN GOOD CONDITION, EXISn NG CONDUIT AND WIRING FOR CANOPY LIGHTS,
<br /> SPANNERS, FASCIA SIGNS, AND I.D./PRICE SIGNS MAY BE REUSED. REROUTE
<br /> SEAL (TYP.) CONDUITS TO STARTER/CONTACTOR BOX VIA ELECTRICAL WAREWAY. RESEAL
<br /> BILL OF MATERIALS
<br /> CONDUITS AS REWIRED PER CODE.
<br /> GALVANIZED RIGID 19 EXISTING CONDUIT NOT REUSED SHALL BE ABANDONED. REMOVE CONDUCTORS.
<br /> ITEM DESCRIPTION QTY. REWARK$
<br /> STEEL CONDUIT (TYP.) THREAD CONDUIT, & CAP BELOW GRADE,
<br /> BUILDING WALL 20. ALL CONDUIT RUNS SHALL BE GROUPED TOGETHER AS MUCH AS POSSIBLE AND
<br /> 1 DISPENSER NEATLY LAIC) PARALLEL IN TRENCHES PATH NO UNNECESSARY CROSS OVERS.
<br /> J OI NEMA IINTERCOUENCLO$URE.TERMINAL BOX OFFMAN GATX NO DEEP
<br /> C)4. _ _ _ _ _ _ _ _ RUNS SHALL BE STRAIGHT EXCEPT MEN CHANGES OF DIRECTION ARE NECCSSARY.
<br /> ITEMS LOCATED IN CASHIER AREA loil
<br /> PVC CONDUIT 21. ELECTRICAL CONDUIT INSTALLED UNDERGROUND SHALL BE 3/4" MINIMUM RICHD
<br /> O CASHIER CONTROL CONSOLE 1 FURNISHED BY CHEVRON (N) INONMETALLIC PVC CONDUIT EXCEPT WHERE PROHIBITED BY LOCAL COOS RI
<br /> CEI 3000PVC TO METAL CONDUITOR
<br /> O SITE CONTROLLER, WAYNE +3 SYSTEM 1 FURNISHED BY CHEVRON MINI 017 I COUPLER (TYP.) AUTHORITIES HAVING JURISDICTION. ALL UNDERGROUND CONDUITS SHALL BE
<br /> CONSOLE LABELED WITH METAL TAGS IDENTIFYING POINTS OF ORIGIN.
<br /> 3/4-C, BELDEN #9537 1/2'C, 2#12+GND UNDERGROUND CONDUITS SHALL BE:
<br /> A. ROUTED IN NON-HAZARDOUS AREAS ONLY, OR
<br /> DISPENSER DATA DISTR18UTION BOx 1 FURNISHED BY CHEVRON1`C. 27#14 1'C, 9#12 I8. SEALED IN ACCORDANCE WITH THE LATEST EDITION OF THE N.E,C, ARTICLES
<br /> (INCL. 1 SPARE) I <A91p1 I 501.5 AND 514.
<br /> coNma
<br /> O- PUMP CONTROLLER / POINT OF SALE, WAYNE +3 SYSTEM I FURNISHED BY CHEVRON COnSttE I
<br /> 22. ANY PORTION OF ELECTRICAL WIRING OR EQUIPMENT WHICH IS BELOW THE H
<br /> 3/4"C, 2 #12+GND i - SURFACE OF A CLASS 1 LOCATION AS DEFINED IN N E.C. TABLE 514 Z) $HALL
<br /> D/W + J I v _ GALVANIZED RIGID
<br /> H E.IMAR w BE CONSIDERED TO OI INA CLASS 1, DIVISION 1 LOCATION, N4HICH SHALL EXTEND
<br /> 'O LINE LCONDITIONER.0024110OT 2000 VA, TEAL ISOLATION FILTER 7 FURNISHED BY CHEVRON
<br /> MODEL D0241,OO7B HARD WIRED UNIT (N) J 000 PRIMARY I .STEEL CONDUIT
<br /> LINE STATION I AT LEAST 70 THE POINT OF EMERGENCE ABOVE GRADE.
<br /> O I STARTER AND CGNTACTOR BOX WITH DISPENSER 1 FURNISHED BY CHEVRON CON DKTIONER i GROUNDISOLATEr/yW }31
<br /> DISCONNECT SWITCHES CEI3000RECEPTACLES I E.P.O.S. 16 NOTES'
<br /> CONTROL
<br /> (N) SECONDARY F
<br /> EXTERIOR DISPENSER EMERGENCY SHUTDOWN, OIL TIGHT/ I I 1. THREADED RIGID METAL CONDUIT SHALL BE USED FOR THE LAST 2 FEET Of
<br /> e 1 PANEL P PIEL N (N) (N) I DATA LLSTATIONJ odv I .UNDERGROUND RUN TO EMERGENCE PER NEC 514.
<br /> WATER TIGHT/CORROSION T/CORROSION RESISTANT 'S0 D' 9007-NR9ft W/ 9001-KA3
<br /> CABLES 2, UNDERGROUND PVC CONDUIT SHALL BE USED ONLY A$ ALLOWED BY N.E.C. 514-8,
<br /> 2 POSITION SELECTOR - ICH, 50. 0" CAT. #9001-KS^116N2, MOUNT IN ENCLOSURE 50."D" 12 PANEL P P3 L STARTER/CONTACTOR 6 9 / I EXCEPTION N0. 2 AND APPLICABLE LOCAL CODES. VERIFY SUITABIUTY WITH ALL
<br /> C)9 MATH LEGEND PLATE KN-244 1 CAT. #NYAF-1 OR EQUAL P2 BOX (N) MODEM I APPROPRIATE AGENCIES. PVC CONDUIT SHALL BE SCHEDULE 40 OR HEAVIER WITH
<br /> Q 10 INTERCOM MAIN STATION I FURNISHED BY ICHEVRON O CONTROLLER
<br /> SI TFi ALL PORTIONS BURIED A MINIMUM 2 FEET BELOW GRADE. Q
<br /> 3M CAT. N0. 0-20 INTERCOM
<br /> I ELECTRONIC
<br /> INTERCOM REMOTE STATION 3M I TRFUNDSANSFER I G16 CONDUIT STUB-UP
<br /> 11 WEATHER RESISTANT SPEAKER/MIC. WITH CALL SWATCH 4 FURN15HED BY ICHEVRON FEEDERS DISPENSER, PUMP PUMP POWER
<br /> & LIGHTING CIRCUITS DISPENSER POWER & LTG,
<br /> EXTERIOR LTG 3 I PRINTER I NO SCALE T.I OTLS\GEN\I6ELECT\If OCOND\16110026 19930804 170600
<br /> 12 CEI 3000 MONITOR/CONTROLLER 1 FURNISHED BY (CHEVRON 3/4"C. 2 #12+GND PUMP PUMP PUMP L __ _ _ _ _ _ _ _ _ _ __ _ J
<br /> CONT. CONT. CONT, 3/4-C, 4#18
<br /> EXISTING PUMP (E) (E) (E) 1/2"C, #8 GND (N) + 2 #14 PER DISPENSER CONCRETE OR ASPHALT
<br /> CONTROLLER
<br /> TO BE REMOVED DISPENSER INTERFACE TO GRADE COVER
<br /> (TYP. FOR 3) ISTDAT TIO 4 FINANCIAL NETWORK
<br /> 8' MADE YELLOW MARKING
<br /> BOX TAPE ALONG TRENCH,
<br /> F 7 1/2"C, DATA CABLES
<br /> ALLEN MFG# AMT-1006-RE. F
<br /> 1'C, DISPENSER DATA-4 /18 PER DI$PIENSER
<br /> BACKFILL MATERIAL: PEA
<br /> GRAVEL (TYP.) BELOW
<br /> CONCRETE OR ASPHALT
<br /> TANK TIWWREWAY GRADE COVER,
<br /> JUNCTIONON BOX
<br /> OX SEE NOTES I AND 2
<br /> NOTE 2 NOTE ..................
<br /> 1. THIS DETAIL PROVIDES ONLY A z
<br /> _ TO PANEL DIAGRAMATIC REPRESENTATION OF =
<br /> GROUND ELECTRICAL EQUIPMENT. THE ACTUAL ry
<br /> FIELD MOUNTING ARRANGEMENT MAY VARY.
<br /> TOP
<br /> -< JTANK DISPENSER POWER, 2 171E TANK MONITOR SENSOR CABLES ARE CONDUIT U 3' MIN EE
<br /> MONITORING EXTERIOR LIGHTING PART OF AN INTRINSICALLY SAFE SYSTEM.
<br /> E SENSORS &PUMP POWER A DO NOT MIX THESE CABLES WTH ANY OTHER
<br /> POWER OR DATA CABLES, 3" MIN--+{
<br /> NOTES:
<br /> 1, BACK FILL AND COMPACTION FOR ALL CONDUIT TRENCHES TO MEET
<br /> STATE, CITY, COUNTY, AND LOCAL REQUIREMENTS.
<br /> 2. BACKIFLL AND COMPACTION FOR SERVICE LATERAL CONDUIT TRENCH TO
<br /> MEET LOCAL ELECTRIC UTIUTY COMPANY REQUIREMENTS IF SOIL 15 NOT
<br /> D
<br /> ROCK FREE. ADD C TO DEPTH OF SERVICE LATERAL CONDUIT TRENCH p
<br /> j
<br /> D4 CONDUIT DIAGRAM D16 CONDUIT TRENCH
<br /> I
<br /> NO SCALE F:\CAD\0726\CONOGRM
<br /> NO SCALE '.I DTS\GEN\I6ELECT\I I000N0\I611003G 19930804.171431 MARK DATE REWSIK:NB ITVT1'TAL
<br /> CONDUIT DIAGRAMS
<br /> AND SITE DETAILS
<br /> c 9-2896 1C
<br /> 25650 HIGHWAY 99 NORTH
<br /> ACAMMPO, CA.
<br /> ul
<br /> Chevron
<br /> N
<br /> 00
<br /> Northwest Region B
<br /> f< B
<br /> 00
<br /> o ROBERT H. LEE & ASSOCIATES, INC.
<br /> 1137 NORTH McDOWELL BOULEVARD PETALUMA CA. 94954 (707) 765-1660
<br /> rn AncHTT,racTURe eNOIN®alNm envfTOAM4eNrrAL aERvlcee
<br /> JOHN W, JOHNSON, ARCHITECT JAMES H. RAY, CIVIL ENGNEER
<br /> RIR, REVIEW "TIAL DATE DATE: 8/22/93
<br /> PRELIMINARY
<br /> N PLANNING DR. BY.
<br /> W
<br /> A STEEL &0
<br /> BLDG PERMIT APPR,: 9G A
<br /> 00
<br /> o GENERAL 810 RHL 1 8344.10
<br /> PERMIT REVS
<br /> Z
<br /> 4
<br /> c3 CONSTRUCTION SHEET
<br /> Z - Do not use droning E-Z
<br /> for construction
<br /> Q
<br /> unless Initbled
<br /> O
<br /> 1 2 3 4 S 6 7 8 9 10 11 12 13 14 15 145 17 18 19 20 ILI 21