- 7 - <br /> Veeder-Root ISD System Specifications <br /> TLS Console & ISD Software Version Number <br /> The ISD audible alarm shall be installed at a location that is most likely to be occupied <br /> by the station attendant during normal station operation (ie. cash register) to hear the <br /> alarm. The TLS console shall be installed in a location that allows the RS232 port to <br /> be easily accessible, and if applicable, per district requirements, for use at anytime. A <br /> vacant RS232 serial port shall always be available to electronically download reports. <br /> The presence of ISD and the ISD software version number can be verified on the TLS <br /> Console LCD screen by using the <STEP> key or by using the TLS Console <PRINT> <br /> key to print and review the latest ISD Daily Report. See Figure 26-7 and 2B-8 for TLS <br /> and ISD verification instructions. <br /> The TLS Console must have a printer as well as an RS232 interface port. <br /> If the TLS is equipped with security features which prohibit access to the TLS, <br /> instructions to override these security features shall be maintained on site in accordance <br /> with air district requirements and shall be available to the air district upon request. <br /> Operability Test Procedure <br /> The Veeder-Root ISD operability test procedure provided in Exhibit 9, and in section 4 of <br /> the ARB Approved Installation, Operation and Maintenance Manual, shall be used <br /> at GDF sites to determine the operability of the Veeder-Root ISD system to comply with <br /> applicable performance standards and performance specification in CP-201. Testing <br /> the ISD equipment in accordance with this procedure will verify the proper selection, <br /> setup and operation of the TLS Console sensors and interface modules. <br /> The Vapor Flow Meter <br /> The Veeder-Root ISD system requires one Vapor Flow Meter per dispenser installed <br /> via the ARB Approved ISD Vapor Flow Meter Manual 577013-796, Rev. E for the <br /> Veeder-Root ISD System. The Vapor Flow Meter shall be installed into dispensers <br /> listed in Exhibit 1 of this Executive Order in accordance with the ARB Approved <br /> Installation, Operation and Maintenance Manual. The Vapor Flow Meter is an <br /> intrinsically safe sensor that is wired to the TLS Console Smart Sensor Module via a <br /> conduit dedicated to TLS Console low-voltage sensors. Figure 2B-9 shows the ISD <br /> Vapor .Flow Meter. Figures 26-13 and 26-14 show the installation configuration. <br /> Healy Phase 11 EVR System Including Veeder-Root ISD, Exhibit 2—VR-202-D <br />