Laserfiche WebLink
Praxair Services, Inc. vl <br /> Technical Solutions for the Industrial World, <br /> UC/SCO EIVViRONME(v7 HEALTh' <br /> Tracer Research Corrocon <br /> TRACER TIGHT TEST RESULTS PERPfl7/SERVICES <br /> Client Date: L,• o — Site Info: Job No: 37969EL <br /> McMaster& Overman, Inc. 7-11 Store 32190 <br /> 1101 W. Graythorn PI. 4943 S. SR 99 <br /> Oro Valley, AZ 85737 Stockton, CA <br /> SYSTEM STATUS System Status -( Pass/Fail) <br /> Product/System Size Tracer Line Tank <br /> 87 Unleaded 14,800 A Pass Pass <br /> 89 Mid-grade 9,700 A Pass Pass <br /> 91 Premium 9,700 A Pass Pass <br /> 0 0 <br /> 0 0 <br /> 0 0 <br /> VR/Vent Amron 2" A Pass <br /> UDCs 6 A Pass <br /> Soil permeability is greater than 89.1 darseys. <br /> GROUND WATER AND PRODUCT INFO <br /> Ground Water Tank <br /> Product I System H2O(In) Product(In) (in) Bottom (in) Tank Top(in) <br /> 87 Unleaded 0 72.2 >120" 0 57 <br /> 89 Mid-grade 0 41.1 >120" 0 57 <br /> 91 Premium 0 30.2 >120" 0 57 <br /> 0 0 0 >120" 0 0 <br /> 0 1 0 1 0 >120" 0 0 <br /> 0 1 0 1 0 >120" 0 0 <br /> TEST EVENTS <br /> INSTALLATION ON-SITE TESTING (inoculation, Sample,Analysis) <br /> PILL BUCKET - H2O TEST <br /> TANK Fill Bucket Pass/Fall apor Recovery Bucket Pass/Fail <br /> 87 Unleaded Fail Pass <br /> 89 Mid-grade Pass Pass <br /> 91 Premium Fail Pass <br /> 0 0 0 <br /> 0 0 0 <br /> 0 0 0 <br /> 1 declare under penalty of perjury that I am a licensed tank tester in the State of California and that the <br /> information contained in this report is true and correct to the best of my knowledge <br /> Tester: Jim Cook State Lic.# 03-1639 <br /> Signature: Date: 212105 <br /> 1 of 4 37969EL-stockton,ca <br />