Laserfiche WebLink
• 6 010 [RECEIVED <br /> S WRCB,January 2002 Page 1 0l'] <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES MAY 2 2 2014 <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes F_ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested r <br /> ENWRONMENTAL <br /> HEAUTHDRAEMAIENI <br /> Test Method Developed By: F Spill Bucket Manufacturer W Industry Standard Professional Engineer <br /> r Other(Specify): <br /> Test Method Used By: Pressure Vacuum r Hydrostatic <br /> r Other(Specify): <br /> Test Equipment Used: LAKE TEST Equipment Resolution:0,0625 in. <br /> Spill Box#Tank T4 Spill Box#Tank T5 Spill Box#Tank T6 <br /> RUL-Fill I -Direct- MUL-Fill I -Direct- PUL-Fill I -Direct- <br /> Grade level in Grade level in Grade level in Spill Box <br /> containment sump containment sump containment sump <br /> Bucket Diameter: 12.00 12.00 12.W <br /> Bucket Depth: 13.00 13.00 13.00 <br /> Wait time between applying <br /> pressure/vacuum/water and I min 1 min I min min <br /> starting test <br /> Test Start Time: 12:00:00 12:00:00 12:00:00 <br /> Initial Reading(RI): 12.00 in. 12.00 in. 12.75 in. <br /> Test End Time: 13:00:00 13:00:00 13:00:00 <br /> Final Reading(110 12.00 in. 12.00 in. 12.75 in. <br /> Test Duration: I hr 1 hr 1 hr <br /> (Rr-R1): 0.00 in. 0.00 in. 0.00 in. <br /> Pass/Fail Threshold or Criteria: +/-0.00 +/-0.00 +1-0.00 +_ <br /> Test Result. Pass Pass Pass <br /> Comments-(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2317293 <br />