Laserfiche WebLink
SAN ti70AQLJI N' LOCAL. HEAT.rrH D=SaTZ1(=r <br /> SMELING PROTQCAL FOR ROUTINE TANK REMOVAL <br /> The following represents minimum sampling criterion required for closure compliance. If <br /> contamination is documented during closure, an Unauthorized Release notification must be <br /> filled out and submitted to SJLHD within 5 days. Section 2652, OCR. <br /> WAT_s14T PRESENT IN TFC TANK PIT <br /> TANK SIZE MINIMUM NURSER OF LOCATION OF SOIL SAMPLES <br /> SOIL SAMPLES <br /> Less than 1000 gallons ONE per tank Fill or pump end of tank <br /> 1000 - 10,000 gallons TWO per tank One at each end of tank <br /> 10,001 gallons and up THREE OR MORE Ends and Middle or <br /> per tankenerally spaced along <br /> ?he length of the tank <br /> t PIPIng ONE EVERY 20 LINEAL FEET <br /> WATER IS REFOM IN TANK PIT <br /> TANK SIZE MINIMUM NO. OF LOCATION OF SOIL MINIMUM NUMBER <br /> SOIL SAMPLES SAMPLES OF WATER SAMPLES <br /> 10,000 GALLONS From wall next to <br /> OR LESS tank ends at soil/ <br /> (Single Tank) TWO groundwater ONE <br /> interface <br /> GRPATER THAN From wall next to ONE <br /> 10,000 GALLONS tank ends at soil./ <br /> OR groundwater <br /> TANK CLUSTER FOUR interface <br />