Laserfiche WebLink
0 <br /> Pacific Bell: 2600 Camino Ramon, Room 3E000, San Ramon, CA 94583 <br /> ROUTINE MONITORING PROCEDURES <br /> Section 2632(d)(1)Title 23 CCR, Chapter 16 <br /> UNDERGROUND FUEL, STORAGE TANK <br /> Facility Name: Pacific Bell (UER47) <br /> Facility Address: 4051 NEWTON ROAD, STOCKTON <br /> UST Installed: Double Wall Composite 10,000 Gallons Containing Gasoline Fuel for Fleet <br /> Refueling. <br /> Piping Installed: Double Wall "Enviroflex" non-metallic flexible piping system for the product <br /> supply and return lines. <br /> A. The Frequency of Performing the Monitoring: <br /> Monitoring is performed continuously on the: <br /> Double wall UST Interstitial space and its two sumps. <br /> B. The methods and equipment used to perform continuous monitoring are: <br /> • VEEDER ROOT UST Monitoring System Model # TLS-350 <br /> • Site fax modem <br /> • GPH magnetostrictive in-tank volumetric probe Model # 847390-107 <br /> • Floating liquid sensors in the: <br /> 1. UST Annular space sensor Model # 794390-420 <br /> 2. Piping sump sensor Model # 794390-205 <br /> 3. Fill sump sensor Model # 794390-205 <br /> 4. Dispenser Containment sensor Model # 794390-420 <br /> 1:1HAZMATPACBELUFORMSlSBC Monitor Plan Merge.doc <br /> Printed: December 6, 2001 page 2 <br />