Laserfiche WebLink
ELECTRICAL NOTES <br />1. SUPPLY AND INSTALL IN ACCORDANCE WITH MANUFACTURERS <br />SPECIFICATIONS LEAK DETECTION AND TANK LEVEL MONITOR <br />SYSTEM, THE SYSTEM SHALL BE TESTED IN ACCORDANCE <br />WITH STATE, FEDERAL AND MFG's SPECIFICATIONS. <br />2. INSTALL DEDICATED 3/4' CONDUITS TO EACH SUBMERGED PUMP <br />ROUTE CONDUIT UNDERGROUND TO MIRE GUTTER AND PROVIDE <br />EY5 SEALS AT ENTRANCE AND EXIT OF ALL CONDUITS. <br />3. INSTALL 3/4' CONDUIT FOR COMMUNICATIONS TO CRIND SYSTEM <br />ROUTE CONDUIT UNDERGROUND TO WIRE GUTTER AND <br />PROVIDE EYS 5EAL5 AT ENTRANCE AND EXIT OF ALL CONDUITS <br />ROUTE OVERHEAD TO MONITORING PANEL. <br />4. INSIAIJ SN' CONDUIT 10 TANK GAUGL IF APPL ICAULE <br />ROUTE CONDUIT UNDERGROUND TO WIRE GUTTER AND PROVIDE EYS <br />SEALS AT ENTRANCE AND EXITS OF ALL CONDUITS. ROUTE OVER <br />READ TO MONOTIRING PANEL. <br />5. INSTALL 3/4' CONDUIT TO DISPEN5ER OR PUMP ROUTE CONDUIT <br />UNDERGROUND TO WIRE GUTTER AND PROVIDE EYS SEALS AT ENTRANCE <br />AND EXIT OF ALL CONDUITS. ROUTE OVERHEAD TO CONTROL CONSOLE. <br />6. IN5TALL NEW EMERGENCY SHUT-OFF SMITH FOR NEW PUMP. <br />AS SHOWN ON PLAN. 3/4' C. TO ELECTRICAL PANEL FOR <br />PUMP DISCONNECT. PROVIDE SIGN STATING 'EMERGENCY SHUT-OFF' <br />IN RED LETTERS WITH CONTRASTING BACKGROUND. <br />7. ALL WIRING TO BE INSTALLED IN EMT. RIGID STEEL OR SCHEDULE 40 <br />PVC CONDUIT WITH GROUND AND SHALL CONFORM TO 1993 NEC AND ALL <br />LOCAL REQUIREMENTS. ALL WIRING SHALL BE IN STRICT ACCORDANCE <br />WITH ARTICLE 513 8 514 OF THE NEC 1993. <br />8. MINIMUM WIRE SIZE SHALL BE 416 WITH TW INSULATION AND SHALL <br />of COPPER U.N.O. <br />9. THE ELECTRICAL PLAN 15 DIAGRAMMATIC. CONtRAC70R SHALL INSTALL <br />ALL ELECTRICAL CONDUITS IN THE MOST ECONOMICAL MANNER POSSIBLE. <br />10. ALI. 'J' BOXES ARE TO BE EXPLOSION PROOF AND TESTED. PROVIDE <br />EY5 SEALS AS REQUIRED BY THE 1993 NEC. <br />11. NFPA 70 REQUIRES THAT YOU CONNECT EACH UNIT TO SYSTEM GROUND <br />EACH PUMP OR DISPENSER SHALL BE CONNECTED TO AN EQUIPMENT <br />GROUNDING CONDUCTER LOCATED IN THE CONDUIT. <br />12. SFAL EACH CONDUIT ENTERING AND EXITING EACH DISPENSER IN <br />STRICT ACCORDANCE W17H NFPA 70 SECTION 501.5. SEAL BY POURING <br />SEALING COMPOUND INTO LEG OF 'Y' FITTING. THE COMPOUND THICKNESS <br />SHALL NOT BE LESS THAN THE TRADE SIZE OF THE CONDUIT AND IN NO <br />CASE LESS THAN 5/8' (REFERENCE NEPA 70 SECTION 510.5 (C-3)) <br />13. PROVIDE VIRE NUTS OR LU05 TO MAKE GOOD CONNECTIONS. CAP ALL <br />UNUSED WIRES. <br />14. PROVIDE PIPE PLUGS TO SEAL UNUSED OPENINGS IN JUNCTION BOXES. <br />1-20,000 GALLON UNDERGROUND <br />DOUBLE WALL FUEL STORAGE TANK <br />REFER TO SHEET F3 O 0 <br />FOR TANK REQUIREMENTS. <br />ASS I GROUP D <br />IIV5ION I.II LOCATION <br />INCON TANK MONITOR <br />PUMP REMOTE CONTROL <br />9OXES TYP OF 3 <br />EXISTING <br />100 A PANEL <br />EMERGENCY PUMP <br />SHUT OFF 8 RESET <br />INTERIOR WALL 0 COUNTER <br />SITE PREPERATION <br />ELECTRICAL REQUIREMENTS ? <br />WIRING <br />3 <br />WIRE ALL DISPENSERS IN ACCORDANCE WITH NFPA 70 AND <br />APPLICABLE, FEDERAL, STATE AND LOCAL CODES AND REGULATIONS. <br />WIRE ALL CIRCUITS NEC CLA55 I. <br />g <br />REOU IREMNETS A'K <br />USE STRANDED COPPER WIRE. THE WIRE MUST BE GAS AND OIL RESISTANT <br />APPROVED FOR 300 VOLT AND FOR 80 C TEMP. <br />GROUNDING <br />NFPA 70 REQUIRES THAT YOU CONNECT EACH UNIT TO SYSTEM GROUND ) <br />THE FOLI.OWING MUST BE CONNECTED TO SYSTEM GROUND IN ACCORDANCE <br />WITH NFPA 70 <br />,� <br />UI SI'L NSERS - SUUMERGED HEROINE PUMPS - RELAY BOX '-YF <br />REQUIREMENTS <br />CIRCUIT BREAKERS y <br />? <br />EACH DISPENSER 15 TO CONNECT TO AN EQUIPMENT GROUNDING <br />CONDUCTOR LOCATED IN THE CONDUIT. THE FOLLOWING APPLIES TO <br />GROUND CONDUCTOR: <br />- USE WIRE. SMALLER 12 AWG <br />- USE WIRE WITH GREEN AND YELLOW STRIPED INSULATION ` <br />- CONNECT TO GREEN GROUNDING SCREW IN JUNCTION BOX', <br />- THE PROVIDING POWER SMALL BE GROUNDED IN ACCORDAN(F' <br />WITH NFPA 70. ARTICLE 250. THE INSTALLER SHOULD ASSURE <br />THAT THE NEUTRAL BUS 15 BONDED TO AN APPROVED EARTH GROUND. 1f, <br />CIRCUIT BREARF.RS J <br />INSTALL SWITCHED NEUTRAL BREAKERS TO EACH CIRCUIT LEADING TO A <br />PUMP OR DISPENSER OR GROUP OF 015PEN5ER5 AND STP 's. THEYIMU5T BE 'g <br />CAPABLE OF SIMULTANEOUSLY DISCONNECTING HOT AND NEUTRAL;,CmONDUCTOR5. <br />DO NOT USE SINGLE POLE BREAKERS WITH HANDLE TIES. <br />REOUIREMENT5 <br />- USE ONLY U.L LISTED CIRCUIT BREAKERS AND CIRCUIT BREAKER PANEL. <br />i Y <br />- INSTALL CIRCUIT BREAKER AWAY FROM PUMPS OR DISPENSERS. THEY MUST <br />BE EASY TO REACH AND CLEARLY MARKED. <br />- INSTALL A 5EPERATE CIRCUIT BREAKER FOR EACH SUBMERGED TURBINE <br />PUMP <br />coNDulTs -' <br />- NEVER USE KNOCK -OUT BOXES OR FLEXIBLE CONDUIT <br />J 4` <br />UNCTION BOXES USED MUST BE U.L. ROOFED FOR <br />CLA55 I C AND D EXPLOSION PROOF. <br />- ALL ELECTRICAL FITTINGS AFTER CONDUIT COMES OUT <br />OF THE CONCRETE OR EARTH MUST BE SEALED I <br />- RUN ALL POWER AND LIGHT WIRES 1N THREADED <br />RIGID METAL CONDUIT OR IN RIGID NON-METALLIC <br />CONDIUT IN CONFORMANCE TO NEC CODES. IF NON- t.'A s ;8 <br />METALLIC CONDUIT 15 USED IT MUST BE AT LEAST <br />IWO FEET UNDERGROUND. 3 <br />- DO NOT RELY ON METAL CONDUIT TO PROVIDE 'A"N <br />EQUIPEMENT GROUND. 1 <br />3/4' CONDUIT FOR <br />SENSORS TYP. <br />3/4' CONDUITS <br />TO WIRE GUTTER <br />/ I <br />/ IG <br />5EN50R <br />NOTE: <br />NEW BUILDINGS OR BUILDING <br />REMODELS ARE NOT PART OF <br />THESE PLANS OR PERMIT <br />r 14� 1 1I Ji u <br />EX15TING OVERHEAD CANOPY <br />0/12 400 MATT SUPER METAL <br />HALIDE FIXTURES <br />D9Z5leQA- 1AWPYnIr VGb- <br />PRODUCI DISPEN5ER5 0/ 2 SIDED <br />CREDIT AND DEBT SINGLE HOSE <br />TYPICAL ( <br />HAZARDOUS AREA NOTES <br />1. IN AN OUTSIDE LOCATION ANY AREA WITHIN 10'-0' <br />HORIZONTALLY FROM ANY TANK FILL PIPE SHALL <br />BE CLASSIFIED AS A CLA55 I DIVISION II <br />HAZARDOUS AREA <br />2. THE AREA 20' OUT FROM DISPENSER AND 4'-0' IN <br />HEIGHT FROM BASE OF DISPENSER SHALL BE CLA55 <br />I DIVISION 1 HAZARDOUS AREA <br />3. ALL ELECTRICAL CONDUITS, FITTINGS, ETC. IN THESE <br />AREAS SHALL CONFORM TO THE LATEST EDITION OF N.E.C. <br />ARTICLE 514. ELECTRICAL WIRING AND EQUIPMENT BELOW <br />A HAZARDOUS AREA SHALL BE RATED FOR CLAS5 I <br />DIVISION 1. PROVIDE SEAL -OFF FITTINGS ON ALL <br />CONDUITS ENTERING OR LEAVING A HAZARDOUS AREA. <br />CONNECT TO EXISTING CIRCUITS <br />NO NEN LOAD VERIFY III <br />CLA55 I DIVISION I, 11 <br />LOCATION 20' RADIUS UP TO 18' <br />ABOVE GRADE FROM EDGE OF <br />DISPENSERS ; <br />EMERGENCY SHUT-OFF SWITCH <br />PROVIDE SIGN STATING <br />'EMERGENCY SHUT OFF <br />IN <br />RED LETTERS ON CONTRASTING <br />BACKGROUND MIN 25' NA%. 75' <br />DESIGN <br />I. <br />SEALS <br />INSTALL <br />iw <br />3/4' <br />C. <br />�EY5 <br />PER <br />NEC 514 <br />/,{---- <br />EX15TING OVERHEAD CANOPY <br />0/12 400 MATT SUPER METAL <br />HALIDE FIXTURES <br />D9Z5leQA- 1AWPYnIr VGb- <br />PRODUCI DISPEN5ER5 0/ 2 SIDED <br />CREDIT AND DEBT SINGLE HOSE <br />TYPICAL ( <br />HAZARDOUS AREA NOTES <br />1. IN AN OUTSIDE LOCATION ANY AREA WITHIN 10'-0' <br />HORIZONTALLY FROM ANY TANK FILL PIPE SHALL <br />BE CLASSIFIED AS A CLA55 I DIVISION II <br />HAZARDOUS AREA <br />2. THE AREA 20' OUT FROM DISPENSER AND 4'-0' IN <br />HEIGHT FROM BASE OF DISPENSER SHALL BE CLA55 <br />I DIVISION 1 HAZARDOUS AREA <br />3. ALL ELECTRICAL CONDUITS, FITTINGS, ETC. IN THESE <br />AREAS SHALL CONFORM TO THE LATEST EDITION OF N.E.C. <br />ARTICLE 514. ELECTRICAL WIRING AND EQUIPMENT BELOW <br />A HAZARDOUS AREA SHALL BE RATED FOR CLAS5 I <br />DIVISION 1. PROVIDE SEAL -OFF FITTINGS ON ALL <br />CONDUITS ENTERING OR LEAVING A HAZARDOUS AREA. <br />CONNECT TO EXISTING CIRCUITS <br />NO NEN LOAD VERIFY III <br />CLA55 I DIVISION I, 11 <br />LOCATION 20' RADIUS UP TO 18' <br />ABOVE GRADE FROM EDGE OF <br />DISPENSERS ; <br />EMERGENCY SHUT-OFF SWITCH <br />PROVIDE SIGN STATING <br />'EMERGENCY SHUT OFF <br />IN <br />RED LETTERS ON CONTRASTING <br />BACKGROUND MIN 25' NA%. 75' <br />�� /+— 3/4' C. 5EN50R/LEVEL PROBE <br />I <br />wuI <br />YL, <br />0 <br />Z <br />ScAuI: 100141-00 <br />MELENDEZ <br />DESIGN <br />GROUP <br />SEALS <br />INSTALL <br />iw <br />3/4' <br />C. <br />�EY5 <br />PER <br />NEC 514 <br />/,{---- <br />MOUIiS'I'0, CA 95355 <br />-- <br />1,1C. 049395 <br />3/4' C. <br />HUL71 PRODUCT DISPENSER <br />C. <br />SENSOR/LEVEL <br />PROBE <br />j1-- <br />3/4' C. <br />MULTI PRODUCT DISPENSER <br />SENSOR/LEVEL <br />PROBE AS REQUIRED <br />3/4' <br />C. <br />SENSOR/LEVEL <br />3/4' C. <br />FUTURE DISPENSER <br />rlN <br />a w <br />DRAWINGS PREPARED FOR: <br />PACIFIC <br />CAR WASH <br />4,105 Pacific Avenue <br />Stockton, Ca 95207 <br />(209) 478-5504 <br />DRAWNRM <br />SHEET <br />CHECKED BY <br />DAT <br />1 1/2' <br />5UBMER51BLE TURBINE <br />JOB e p, 3017 <br />1 1/2' <br />5USMER51BLE TURBINE <br />3/4' C. <br />CANOPY LIGHTS <br />/}--- <br />3/4' C. <br />CANOPY LIGHTS <br />/+— <br />3/4' C. <br />CANOPY LIGHTS <br />/+ — <br />3/4" C. <br />CANOPY LIGHTS <br />�� /+— 3/4' C. 5EN50R/LEVEL PROBE <br />I <br />wuI <br />YL, <br />0 <br />Z <br />ScAuI: 100141-00 <br />MELENDEZ <br />DESIGN <br />GROUP <br />F11 ill NfltNi111. lAMI{• {'n N. 9llli)CIIONMANAiII!MFNI <br />• CNVIRIIMP N I AI..51'R VH I'A • <br />ln1111141IISIIN AVP NTH PIIIIOx 7/4144 <br />II 01KI N 1'Ag4ISA AIII0I'ANI.CA971II1 <br />iw <br />3/4' <br />C. <br />SENSOR/LEVEL <br />PROBE <br />/,{---- <br />MOUIiS'I'0, CA 95355 <br />(209)529-4652 <br />1,1C. 049395 <br />CONTRACTOR: <br />3/4' <br />C. <br />SENSOR/LEVEL <br />PROBE <br />> <br />/#-- 3/4' <br />C. <br />SENSOR/LEVEL <br />PROBE AS REQUIRED <br />3/4' <br />C. <br />SENSOR/LEVEL <br />PROBE <br />�� /+— 3/4' C. 5EN50R/LEVEL PROBE <br />I <br />wuI <br />YL, <br />0 <br />Z <br />ScAuI: 100141-00 <br />MELENDEZ <br />DESIGN <br />GROUP <br />F11 ill NfltNi111. lAMI{• {'n N. 9llli)CIIONMANAiII!MFNI <br />• CNVIRIIMP N I AI..51'R VH I'A • <br />ln1111141IISIIN AVP NTH PIIIIOx 7/4144 <br />II 01KI N 1'Ag4ISA AIII0I'ANI.CA971II1 <br />..Ir.,. (209) B52-0170 n. (209) 852-2014 <br />ENGINEER: <br />TI IONIAS <br />NIOCI IIGUKI <br />E'NGINE'FItING <br />2909 LAI<ANU UIZIVI; <br />MOUIiS'I'0, CA 95355 <br />(209)529-4652 <br />1,1C. 049395 <br />CONTRACTOR: <br />SHEET TITLE <br />01 0, r!'ri1 GA "j <br />I WA A <br />REVISIONS <br />No. <br />Dot. <br />By <br />Ca mm�nls <br />DRAWINGS PREPARED FOR: <br />PACIFIC <br />CAR WASH <br />4,105 Pacific Avenue <br />Stockton, Ca 95207 <br />(209) 478-5504 <br />DRAWNRM <br />SHEET <br />CHECKED BY <br />DAT <br />SCALENO SCALE <br />1J v <br />JOB e p, 3017 <br />