Laserfiche WebLink
SWRCB,January 2002 Page 5 of 5 <br /> 8.FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used ❑ Pressure ❑ Vacuum N Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used:Incon TS-STS Equipment Resolution: .0006 <br /> Fill Sump#Middle Fill Sump# Fill Sump# Fill Sump# <br /> UE042UO01 UE042U001 <br /> Sump Diameter: 38" 38" <br /> Sump Depth: 41" 40.5" <br /> Height from Tank Top to Top of NIA 10" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 14" 8" <br /> Electrical Penetration: <br /> Condition of sum prior to testing: Good Good <br /> Portion of Sump Tested: 2"Above Collar <br /> Sumv Material: Fiber lass Fiberglass <br /> Wait time between applying 15 Min <br /> pressure/vacuum/water and starting <br /> test: <br /> Test Start Time.. 10:20 AM 10:36 AM <br /> Initial Reading i : 2.9936 2.9938 <br /> Test End Time: 10:35 AM 10:51 AM <br /> Final Reading 2.9937 2.9935 <br /> Test Duration: 15 Min 15 Min <br /> Chanize in Reading f-Ri : .0001 .0003 <br /> Pass/Fail Threshold or Criteria: .002 .002 <br /> Test Result: ® Pass ❑ Fail ❑ Pass ® FaiI ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Is there a sensor in the sump? ® Yes ❑ No ® Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No <br /> Does the sensor alarm when either ❑ Yes ® No ❑ NA ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> roduct or water is detected? <br /> Was sensor removed for testing? ® Yes ❑ No ❑ NA ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> Was sensor properly replaced and ❑ NA ❑ Yes ❑ No ❑ NA [IYes ❑ No ❑ NA <br /> verified functional after testing? Elly:111 <br /> ® No ❑ NA 11P Yes ® No <br /> Comments include any information on re airs made prior to testing,and recommended follow-up for failed tests <br /> The Middle Sump sensor were reinstalled to the lowest point,but not tested. <br /> The Fill Sump is a visual failure due to the Vent Secondary cracked test boot.Did not put any test water into the fill sump. <br />