DISPENSER CONTROL WIRING <br />LIGHTING CONTROL WIRING <br />GENERAL NOTES FOR LIGHTING CONTROLS: <br />1 - OVERCURRENT PROTECTION FOR EACH LIGHTING CIRCUIT TO BE CONTROLLED IS <br />PROVIDED BY OTHERS. THIS OVERCURRENT PROTECTION SHALL BE LIMITED TO <br />30 AMPS MAXIMUM FOR EACH CIRCUIT UNLESS OTHERWISE SPECIFIED. <br />2 - CONTROL FUSE "Li" FOR LIGHTING CONTROL POWER MUST BE "5 AMPS. REPLACE <br />WITH THE SAME TYPE RATING AND FUSE. <br />LIGHTING CONTROL EQUIPMENT SHEET <br />RF EQUIPMENT VOLTS CONTACTOR PANEL OUT <br /># NUMBER; AMPS CIRCUITS, PUT <br />1 TOPPER LTG. -.. _.. 120 <br />2 CANOPY LIGHTS #1 120 1 30 A-3 SW -1 <br />3 CANOPY LIGHTS #2 120 A-5 <br />4 CANOPY LIGHTS #3 120 A-9 <br />5 CANOPY LIGHTS #4 120 A-11 <br />6 CANOPY LIGHTS #5 (FUTURE) 120 2 30 A-15 SW -1 <br />7 CANOPY LIGHTS #6((FUTURE)) 120 A-27 <br />8 CANOPY LIGHTS #7 FUTURE 20 A-29 <br />9 SIGNS / FASCIA #1 120 A-17 <br />10 SIGNS /FASCIA #2 120 3 30 A-21 ;SW -2 <br />11 <br />12_ _ <br />SWITCHES ARE <br />MOUNTED ON DOOR. <br />CANOPY LIGHTS SIGNS/FASCIA <br />OFF ON OFF _ ON <br />1 2 3 4 <br />REFER TO EQUIPMENT SHEET <br />FOR ALL CONTACTOR WIRING. <br />**LINE SIDE IS PRE WIRED A <br />SQUARE D TO CIRCUIT Ell <br />5 6 7 8 <br />3M I (30A <br />9 10 11 12 <br />30A <br />TO PANEL "A" NEUTRAL BAR <br />10 <br />PUMP <br />PUMP <br />2 <br />�PL ) <br />PUMP <br />3 <br />I <br />PL <br />PUMP <br />4 <br />-I I <br />PL j <br />I <br />RESET SWITCH <br />NOTIFICATION <br />SURGE MODULE <br />FAILURE <br />I PL <br />-- ---- ---- ---- <br />r_--_ _ _ --_ _ _ ___ ___ _ ___ ___ _-_____, <br />I ' <br />----- <br />Il r----- -- ------ --- - -- ---- ----1 <br />I I I I 11' 1 1 <br />I I I I I I I I I I <br />I I I I I MM ���� <br />11 I /12'A% GILSARCO D -BOX i t <br />11 I I I <br />I I I I I <br />I I I I I <br />75 <br />read 4 <br />B 1 2 3 4 <br />PUMPS <br />I I <br />I I I I I <br />I I I I I <br />`---- <br />L — — —— <br />' <br />6 <br />I I I <br />� � I <br />I I <br />#14 TWISTED PAIR PER I I 1 <br />MANUFACTURER'S SPECIFICATIONS <br />aaF DATA it ___ J I 1 -------------- <br />--------- <br />___ _ _ J I L--------------- <br />_ <br />WD- - ----- --- ----L�------ -- <br />DISPENSER AI TREADER !----------------------- <br />-1- <br />DATA (DC) WIRINNG 3 <br />12 <br />TYPICAL DISPENSER FIELD WIRING TO EACH MODULE <br />RIBBON CABLE <br />TO ADDITIONAL <br />0 DISPENSER MODULES <br />DM—EX MODULE FOR DISPENSER ##1 <br />FROM <br />TERMINAL STRIP <br />SHOWN ABOVE <br />(BREAKOUT MODULE) <br />PATENT <br />PENDING' <br />000 <br />NETWORK BUS <br />P <br />ATMR5 <br />FI <br />ATN <br />1. <br />FUSE <br />FU <br />FROM <br />TERMINAL STRIP <br />SHOWN ABOVE <br />(BREAKOUT MODULE) <br />P2, (i P3, (i P4 <br />PM <br />STANDARD EM01 <br />FUEL SHUTDOWN <br />J <br />SWITCH <br />0 0 <br />REMOTE EMERGENCY SHUTDOWN BUTTON <br />FIELD INSTALLED BY CONTRACTOR AT <br />REMOTE PLANTER AREA JUMPER AT <br />SQUARE D IPaCS FOR TESTING <br />REMOTE EMERGENCY SHUTDOWN BUTTON <br />FIELD INSTALLED BY CONTRACTOR AT <br />OUTSIDE OF BUILDING JUMPER AT <br />SQUARE D IP°CS FOR TESTING <br />Tn DDCAI/rD 110 nAl nnAlllAn r- •- a - <br />E -STOP E-STCP <br />L---------------, <br />WARNING <br />I <br />PROPER JUMPER PLACEMENT IS CRITICAL FOR THE j <br />CORRECT OPERATION OF THE FUELING CONTROLS. REFER I <br />TO 8-1/2" X 11" DETAIL SHEETS IN BOOK FOR THE I <br />CORRECT APPUCATION I <br />I ' <br />FACTORY INSTALLED JUMPERS MUST BE PLACED IN I ' <br />POSITION SHOWN FOR F.E. PETRO "IST-VFC"/ RED I I <br />JACKET "CPT" SYSTEMS - DO NOT REMOVE JUMPERS <br />I <br />r- - <br />I I <br />I I <br />E I ' n <br />I I <br />I I <br />l { I I <br />TYPICAL OF ALL DM—EX MODULES <br />F_I <br />SCALE: NTS <br />C <br />CONNECT <br />RIBBON CABLE <br />TO DM -EX <br />MODULE #1 <br />(TOP RIGHT <br />NETWORK BUS) <br />TO BREAKER & NEUTRAL BAR <br />FOR DISPENSER #1 POWER <br />TYPICAL OF ALL DM -EX MODULES <br />(20 AMP MAX - #12 AWG.) <br />PATENT <br />PENDING' <br />000 <br />NETWORK BUS <br />>: <br />C <br />1. <br />-® <br />BRFAY <br />INP <br />INPUT - <br />P2, (i P3, (i P4 <br />PM <br />STANDARD EM01 <br />FUEL SHUTDOWN <br />J <br />SWITCH <br />0 0 <br />REMOTE EMERGENCY SHUTDOWN BUTTON <br />FIELD INSTALLED BY CONTRACTOR AT <br />REMOTE PLANTER AREA JUMPER AT <br />SQUARE D IPaCS FOR TESTING <br />REMOTE EMERGENCY SHUTDOWN BUTTON <br />FIELD INSTALLED BY CONTRACTOR AT <br />OUTSIDE OF BUILDING JUMPER AT <br />SQUARE D IP°CS FOR TESTING <br />Tn DDCAI/rD 110 nAl nnAlllAn r- •- a - <br />E -STOP E-STCP <br />L---------------, <br />WARNING <br />I <br />PROPER JUMPER PLACEMENT IS CRITICAL FOR THE j <br />CORRECT OPERATION OF THE FUELING CONTROLS. REFER I <br />TO 8-1/2" X 11" DETAIL SHEETS IN BOOK FOR THE I <br />CORRECT APPUCATION I <br />I ' <br />FACTORY INSTALLED JUMPERS MUST BE PLACED IN I ' <br />POSITION SHOWN FOR F.E. PETRO "IST-VFC"/ RED I I <br />JACKET "CPT" SYSTEMS - DO NOT REMOVE JUMPERS <br />I <br />r- - <br />I I <br />I I <br />E I ' n <br />I I <br />I I <br />l { I I <br />TYPICAL OF ALL DM—EX MODULES <br />F_I <br />SCALE: NTS <br />C <br />CONNECT <br />RIBBON CABLE <br />TO DM -EX <br />MODULE #1 <br />(TOP RIGHT <br />NETWORK BUS) <br />TO BREAKER & NEUTRAL BAR <br />FOR DISPENSER #1 POWER <br />TYPICAL OF ALL DM -EX MODULES <br />(20 AMP MAX - #12 AWG.) <br />B] <br />ALARM CONTACT IN SURGE <br />DIVERSION MODULE. FACTOR <br />WIRED AT SQUARE D IPaCS. <br />SEAL FEATURES FOR FUELING CONTROLS <br />I - TURBINE DISABLE SWITCH <br />A SPST SWITCH LOCATED ON EXTERIOR CABINET DOOR IS PROVIDED TO ALLOW PUMP AUTHORIZATION SIGNAL <br />FROM DMEX MODULE TO BE "OPENED" AND PREVENT TURBINE OPERATION. RELEY "R3" (4P/DT) OPENS THE <br />SIGNALS. WITH SWITCH IN OFF POSITION THE "HOOK" SIGNAL IS PREVENTED FROM REACHING TERMINALS 1A,2A,3A <br />& 4A WHICH PREVENTS NFCS FROM STARTING TURBINES. WITH SWITCH IN ON POSITION TURBINES OPERATE <br />NORMALLY. TYPICALLY USED TO DISABLE TURBINES WHEN FACILITY IS CLOSED. <br />RELAY BASE <br />70OHN121 <br />RELAY CUBE <br />700/HK36A1 <br />/ RELAY R3 CONTACTS SHOWN <br />!!! BELOW 1A, 2A, 3A, 4A TERMINALS <br />CP P1 P2 P3 P4RELAY BASE <br />1 2 3 4 8501NR34 <br />(n) U1) 00 (n) (n) A A A A <br />4 4 4 4 4 RELAY CUBE <br />8501RS44P14V20 <br />.. . 1z) .. <br />z z z z <br />�i <br />I7[,,• �,_,, 1.1 <br />OFF <br />R3 <br />TURBINE DISABLE <br />E -STOP <br />LOCATED ON <br />CABINET DOOR <br />J <br />Isri <br />;m <br />C <br />1. <br />B] <br />ALARM CONTACT IN SURGE <br />DIVERSION MODULE. FACTOR <br />WIRED AT SQUARE D IPaCS. <br />SEAL FEATURES FOR FUELING CONTROLS <br />I - TURBINE DISABLE SWITCH <br />A SPST SWITCH LOCATED ON EXTERIOR CABINET DOOR IS PROVIDED TO ALLOW PUMP AUTHORIZATION SIGNAL <br />FROM DMEX MODULE TO BE "OPENED" AND PREVENT TURBINE OPERATION. RELEY "R3" (4P/DT) OPENS THE <br />SIGNALS. WITH SWITCH IN OFF POSITION THE "HOOK" SIGNAL IS PREVENTED FROM REACHING TERMINALS 1A,2A,3A <br />& 4A WHICH PREVENTS NFCS FROM STARTING TURBINES. WITH SWITCH IN ON POSITION TURBINES OPERATE <br />NORMALLY. TYPICALLY USED TO DISABLE TURBINES WHEN FACILITY IS CLOSED. <br />RELAY BASE <br />70OHN121 <br />RELAY CUBE <br />700/HK36A1 <br />/ RELAY R3 CONTACTS SHOWN <br />!!! BELOW 1A, 2A, 3A, 4A TERMINALS <br />CP P1 P2 P3 P4RELAY BASE <br />1 2 3 4 8501NR34 <br />(n) U1) 00 (n) (n) A A A A <br />4 4 4 4 4 RELAY CUBE <br />8501RS44P14V20 <br />.. . 1z) .. <br />z z z z <br />�i <br />I7[,,• �,_,, 1.1 <br />OFF <br />R3 <br />TURBINE DISABLE <br />E -STOP <br />LOCATED ON <br />CABINET DOOR <br />_A7 <br />TO PANEL "A" BREAKER TO PANEL "A" BREAKER <br />FOR POWER TO PUMP #1 FOR POWER TO PUMP #2 <br />(#10 AWG) (#10 AWG) <br />4 5 8 <br />si -- -CPN -- s2 -CPN -� <br />30A RATING 30A RATING <br />PUMP IPFUMP 1#2 <br />W <br />I 1I <br />TO <br />ITO <br />J CJ <br />_ y NSC" - = 'vsc„ <br />j co <br />`----- (OR) L------- (OR) W 01 <br />"PUMP #1" "PUMP #2" -1 Q <br />=W3 <br />3Q= <br />TO PANEL "A" BREAKER TO PANEL "A" BREAKER -I < <br />FOR POWER TO PUMP #3 FOR POWER TO PUMP #4 �! 0 <br />(#10 AWG) JT O AWG) (NOT USED) 0) Q <br />e a e a O <br />ss -CPN —sa---►CPN <br />30A RATING 30A RATING <br />PUMP 3 PUMP 1 #4 <br />X <br />t TO I I TO L 0 <br />L "USC" i '\/SC" <br />_ 1 <br />-- --- (OR) L----- (OR) fr <br />PUMP #3„ "PUMP #4" LCL <br />(NOT USED) <br />W <br />Q <br />GENERAL NOTES FOR DISPENSER/PUMP CONTROLS _j N <br />SEE NOTE 11 W r <br />BEFORE STARTING THE ASSEMBLY PROCESS PLEASE Ir <br />READ ALL NOTES. Ir- N 0 <br />ALL FIELD WIRING TERMINALS MUST BE WIRED WITH A MINIMUM INSULATION O Q <br />QRATING OF 69C IF CIRCUIT IS RATED LESS THAN 100 AMPS. OR A <br />MINIMUM INSULATION RATING OF 75'C IF CIRCUIT IS RATED OVER 100 � U Q <br />AMPS. ALL MAIN DISCONNECT AND BRANCH CIRCUIT PROTECTION SHALL BE <br />SUBMERSIBLE PUMP EQUIPMENT SHEET PROVIDED BY OTHERS, <br />Q9pFF SSI ONq <br />RF EQUIPMENT VOLTS CONTACTOR PANEL TOUT Q WHEN CONTROLLED LOAD ISA MOTOR, CIRCUITS MUST HAVE THERMAL /?, yPROTECTION INTEGRAL TO c <br />�/ HAL B <br />FE PETRO IST 1 208 NUMBER A30S CIA -14 PST Q THIS D A ING CO T INS ALL <br />LSOHF R FACTORY <br />WIRIN REQ <br />LIRE OFO JI 4 <br />1 <br />3 UNLEADED -1 # A-18 a ALL FIELD WIRING TO THESE CONTROLS PLEASE SEE THE 8-1/2" <br />4 A-20 X 11" DETAIL SHEETS INCLUDED IN THE INSTALLATION BOOK, r9T�0 I V I-\-- <br />5 <br />\- O��\ < <br />6 UN EADED ETROI2T #2 208 2 30 A-24 S2 , Q THE WIRE GAUGE USED TO ASSEMBLE THESE CONTROLS VARIES \f _RF CA IV <br />7 " -i" " A-26 5 THROUGHOUT. TO DETERMINE WIRE SIZE THAT SHOULD BE USED PLEASE <br />8 FE PETRO IST #3 2083 i 30 A-28 S3 CHECK THE AMPERAGE OF THE CIRCUIT CONTROLLING THESE _ <br />COMPONENTS. THE AMPERAGE CAN BE OBTAINED FROM THEa <br />9 PREMIUM - A-30 PANELBOARD SCHEDULES LOCATED IN THIS SET. = r <br />10 A-320 z z <br />11 FE PETRO IST #4 (NOT USED) 208 4 30 A-34 S4 IF THERE ARE ANY QUESTIONS ABOUT THE PLACEMENT OF ANY <br />12 A-36 1 Z� NON-STANDARD DEVICES ON THE DISPENSER/PUMP CONTROL SCREEN <br />DISPENSER DM — E X MODULE CHART PLEASE CONTACT THE MANUFACTURER TO DETERMINE PROPER PLACEMENT. <br />u <br />- WHEN VARIABLE SPEED CONTROLLERS ARE FIELD INSTALLED, THE <br />DISP. BREAKER DESCRIPTION VOLTS AMPS PANEL 7 PLACEMENT OF THE EQUIPMENT SHALL BE DETERMINED BY THE d <br />ELECTRICAL CONTRACTOR. <br />NUMBER CIRCUITS o o 8 0 <br />DM EX #1 DISPENSER 1 120 20 B-1 Q THE STANDARD LIGHTING/DISPENSER MANAGER MODEL IS <br />DM EX #2 DISPENSER 2 120 20 B-5 EXPANDABLE TO 8 DISPENSERS. <br />DM EX #3 DISPENSER 3 120 20 8-9 THE DISPENSER CONTROL WIRING SHOWN ON THIS DRAWING IS FOR ONE <br />DM EX #4 DISPENSER 4 120 20 3-13 A DISPENSER. ALTHOUGH THE NUMBER OF DISPENSERS USED FOR EACH <br />DM EX #5 DISPENSER 5 120 20 B-17 JOB MAY VARY THE WIRING SHOWN IS TYPICAL OF ALL DISPENSERS. _ <br />DM -EX #6 DISPENSER 6 120 20 B-2 <br />DM -FX #7 DISPENSER 7 120 20 B -6Q THE PILOT LIGHTS SHOWN ON THIS DRAWING ARE TO VISUALLY VERIFY THE 7o z w <br />10 OPERATION OF EACH PUMP. ALL PILOT LIGHTS SHOWN SHOULD BE 0 4^ <br />DM -EX #8 _ DISPENSER 8 120 20 B-10 5 <br />MOUNTED ON THE DOOR OF THE DISPENSER/PUMP CONTROLS SECTION, w ¢ a <br />120/208 VOLT COLOR C HART Q THE MOMENTARY SWITCHES FOR "FUEL SHUTDOWN" AND "FUEL RESET" z z w <br />®®®. ®..I®. ®®. ®®.1110111®®:®.�®00AFO �®®�®.��®®®®®.�®�� <br />® / <br />A <br />SHOWN ON THIS DRAWING SHOULD BE MOUNTED ON THE DOOR OF THE ``' N 3 <br />DISPENSER/PUMP CONTROLS SECTION. a o N I, <br />00 Z - <br />QWIRING IS TYPICAL OF ALL DISPENSERS. GROUND CONDUCTOR (#12 AWG) z 0)1 1 w w <br />12 MUST ALSO BE RUN FROM EACH DISPENSER TO THE GROUND BAR OF THE LNa In I, z <br />DISPENSER/PUMP CONTROL PANEL, Lo 3 NN Z <br />13 DISPENSER "AC" (POWER) AND "DC" (DATA) TYPICALLY RUN IN SAME cv z N N <br />CONDUITS, OR PER DISPENSER MANUFACTURERS REQUIREMENTS. DD Y d N <br />1a SEE DISPENSER INSTALLATION DIAGRAMS FOR TERMINATION LABELING. <br />QALL FIELD WIRING TERMINALS MUST BE WIRED WITH A MINIMUM INSULATION c b� <br />s RATING OF 69C. J y <br />s FACTORY INSTALLED "REMOTE OFF" JUMPERS ON DM -EX MODULES MUST Q ?_ 0 <br />REMAIN IN PLACE DURING NORMAL OPERATION. REMOVING THIS JUMPER AND <br />WIRING INTO A "PAN SENSOR" SYSTEM PROVIDES INDIVIDUAL SHUTDOWN OF a <br />NOTE; EACH DISPENSER. Svti <br />d' 1069 <br />* BEFORE WIRING BRANCH CIRCUITS REFER TO PANELBOARD 17 THE WIRE SIZE AND NUMBER CONDUCTORS REQUIRED FOR Go <br />COMMUNICATION/DATA (DC) WIRING MUST BE DETERMINED BY THE <br />SCHEDULES TO DETERMINE THE PHASE COLORS TO BE USED. SPECIFICATIONS of THE DISPENSER MANUFACTURER. TYPICALLY 2 <br />* ALL MAIN DISCONNECT AND BRANCH CIRCUIT PROTECTION CONDUCTORS (NORMALLY SHIELDED CABLE) ARE REQUIRED WHEN CARD <br />SHALL BE PROVIDED BY OTHERS. READERS IN THE DISPENSER ARE USED. <br />T <br />J <br />C <br />O <br />d <br />} <br />Z <br />o <br />O <br />Mir <br />Q <br />O <br />L <br />� <br />W <br />LL <br />z <br />LL <br />O <br />O <br />z <br />= <br />Q <br />U <br />U <br />�sW0< <br />n- <br />cv <br />- <br />L <br />�el�0 <br />$ <br />w <br />"I <br />IU - <br />Y <br />O <br />0 <br />� <br />� <br />N <br />_A7 <br />TO PANEL "A" BREAKER TO PANEL "A" BREAKER <br />FOR POWER TO PUMP #1 FOR POWER TO PUMP #2 <br />(#10 AWG) (#10 AWG) <br />4 5 8 <br />si -- -CPN -- s2 -CPN -� <br />30A RATING 30A RATING <br />PUMP IPFUMP 1#2 <br />W <br />I 1I <br />TO <br />ITO <br />J CJ <br />_ y NSC" - = 'vsc„ <br />j co <br />`----- (OR) L------- (OR) W 01 <br />"PUMP #1" "PUMP #2" -1 Q <br />=W3 <br />3Q= <br />TO PANEL "A" BREAKER TO PANEL "A" BREAKER -I < <br />FOR POWER TO PUMP #3 FOR POWER TO PUMP #4 �! 0 <br />(#10 AWG) JT O AWG) (NOT USED) 0) Q <br />e a e a O <br />ss -CPN —sa---►CPN <br />30A RATING 30A RATING <br />PUMP 3 PUMP 1 #4 <br />X <br />t TO I I TO L 0 <br />L "USC" i '\/SC" <br />_ 1 <br />-- --- (OR) L----- (OR) fr <br />PUMP #3„ "PUMP #4" LCL <br />(NOT USED) <br />W <br />Q <br />GENERAL NOTES FOR DISPENSER/PUMP CONTROLS _j N <br />SEE NOTE 11 W r <br />BEFORE STARTING THE ASSEMBLY PROCESS PLEASE Ir <br />READ ALL NOTES. Ir- N 0 <br />ALL FIELD WIRING TERMINALS MUST BE WIRED WITH A MINIMUM INSULATION O Q <br />QRATING OF 69C IF CIRCUIT IS RATED LESS THAN 100 AMPS. OR A <br />MINIMUM INSULATION RATING OF 75'C IF CIRCUIT IS RATED OVER 100 � U Q <br />AMPS. ALL MAIN DISCONNECT AND BRANCH CIRCUIT PROTECTION SHALL BE <br />SUBMERSIBLE PUMP EQUIPMENT SHEET PROVIDED BY OTHERS, <br />Q9pFF SSI ONq <br />RF EQUIPMENT VOLTS CONTACTOR PANEL TOUT Q WHEN CONTROLLED LOAD ISA MOTOR, CIRCUITS MUST HAVE THERMAL /?, yPROTECTION INTEGRAL TO c <br />�/ HAL B <br />FE PETRO IST 1 208 NUMBER A30S CIA -14 PST Q THIS D A ING CO T INS ALL <br />LSOHF R FACTORY <br />WIRIN REQ <br />LIRE OFO JI 4 <br />1 <br />3 UNLEADED -1 # A-18 a ALL FIELD WIRING TO THESE CONTROLS PLEASE SEE THE 8-1/2" <br />4 A-20 X 11" DETAIL SHEETS INCLUDED IN THE INSTALLATION BOOK, r9T�0 I V I-\-- <br />5 <br />\- O��\ < <br />6 UN EADED ETROI2T #2 208 2 30 A-24 S2 , Q THE WIRE GAUGE USED TO ASSEMBLE THESE CONTROLS VARIES \f _RF CA IV <br />7 " -i" " A-26 5 THROUGHOUT. TO DETERMINE WIRE SIZE THAT SHOULD BE USED PLEASE <br />8 FE PETRO IST #3 2083 i 30 A-28 S3 CHECK THE AMPERAGE OF THE CIRCUIT CONTROLLING THESE _ <br />COMPONENTS. THE AMPERAGE CAN BE OBTAINED FROM THEa <br />9 PREMIUM - A-30 PANELBOARD SCHEDULES LOCATED IN THIS SET. = r <br />10 A-320 z z <br />11 FE PETRO IST #4 (NOT USED) 208 4 30 A-34 S4 IF THERE ARE ANY QUESTIONS ABOUT THE PLACEMENT OF ANY <br />12 A-36 1 Z� NON-STANDARD DEVICES ON THE DISPENSER/PUMP CONTROL SCREEN <br />DISPENSER DM — E X MODULE CHART PLEASE CONTACT THE MANUFACTURER TO DETERMINE PROPER PLACEMENT. <br />u <br />- WHEN VARIABLE SPEED CONTROLLERS ARE FIELD INSTALLED, THE <br />DISP. BREAKER DESCRIPTION VOLTS AMPS PANEL 7 PLACEMENT OF THE EQUIPMENT SHALL BE DETERMINED BY THE d <br />ELECTRICAL CONTRACTOR. <br />NUMBER CIRCUITS o o 8 0 <br />DM EX #1 DISPENSER 1 120 20 B-1 Q THE STANDARD LIGHTING/DISPENSER MANAGER MODEL IS <br />DM EX #2 DISPENSER 2 120 20 B-5 EXPANDABLE TO 8 DISPENSERS. <br />DM EX #3 DISPENSER 3 120 20 8-9 THE DISPENSER CONTROL WIRING SHOWN ON THIS DRAWING IS FOR ONE <br />DM EX #4 DISPENSER 4 120 20 3-13 A DISPENSER. ALTHOUGH THE NUMBER OF DISPENSERS USED FOR EACH <br />DM EX #5 DISPENSER 5 120 20 B-17 JOB MAY VARY THE WIRING SHOWN IS TYPICAL OF ALL DISPENSERS. _ <br />DM -EX #6 DISPENSER 6 120 20 B-2 <br />DM -FX #7 DISPENSER 7 120 20 B -6Q THE PILOT LIGHTS SHOWN ON THIS DRAWING ARE TO VISUALLY VERIFY THE 7o z w <br />10 OPERATION OF EACH PUMP. ALL PILOT LIGHTS SHOWN SHOULD BE 0 4^ <br />DM -EX #8 _ DISPENSER 8 120 20 B-10 5 <br />MOUNTED ON THE DOOR OF THE DISPENSER/PUMP CONTROLS SECTION, w ¢ a <br />120/208 VOLT COLOR C HART Q THE MOMENTARY SWITCHES FOR "FUEL SHUTDOWN" AND "FUEL RESET" z z w <br />®®®. ®..I®. ®®. ®®.1110111®®:®.�®00AFO �®®�®.��®®®®®.�®�� <br />® / <br />A <br />SHOWN ON THIS DRAWING SHOULD BE MOUNTED ON THE DOOR OF THE ``' N 3 <br />DISPENSER/PUMP CONTROLS SECTION. a o N I, <br />00 Z - <br />QWIRING IS TYPICAL OF ALL DISPENSERS. GROUND CONDUCTOR (#12 AWG) z 0)1 1 w w <br />12 MUST ALSO BE RUN FROM EACH DISPENSER TO THE GROUND BAR OF THE LNa In I, z <br />DISPENSER/PUMP CONTROL PANEL, Lo 3 NN Z <br />13 DISPENSER "AC" (POWER) AND "DC" (DATA) TYPICALLY RUN IN SAME cv z N N <br />CONDUITS, OR PER DISPENSER MANUFACTURERS REQUIREMENTS. DD Y d N <br />1a SEE DISPENSER INSTALLATION DIAGRAMS FOR TERMINATION LABELING. <br />QALL FIELD WIRING TERMINALS MUST BE WIRED WITH A MINIMUM INSULATION c b� <br />s RATING OF 69C. J y <br />s FACTORY INSTALLED "REMOTE OFF" JUMPERS ON DM -EX MODULES MUST Q ?_ 0 <br />REMAIN IN PLACE DURING NORMAL OPERATION. REMOVING THIS JUMPER AND <br />WIRING INTO A "PAN SENSOR" SYSTEM PROVIDES INDIVIDUAL SHUTDOWN OF a <br />NOTE; EACH DISPENSER. Svti <br />d' 1069 <br />* BEFORE WIRING BRANCH CIRCUITS REFER TO PANELBOARD 17 THE WIRE SIZE AND NUMBER CONDUCTORS REQUIRED FOR Go <br />COMMUNICATION/DATA (DC) WIRING MUST BE DETERMINED BY THE <br />SCHEDULES TO DETERMINE THE PHASE COLORS TO BE USED. SPECIFICATIONS of THE DISPENSER MANUFACTURER. TYPICALLY 2 <br />* ALL MAIN DISCONNECT AND BRANCH CIRCUIT PROTECTION CONDUCTORS (NORMALLY SHIELDED CABLE) ARE REQUIRED WHEN CARD <br />SHALL BE PROVIDED BY OTHERS. READERS IN THE DISPENSER ARE USED. <br />T <br />