Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for Fast Lane Central Valley as of October03, 2018. <br /> Open violations from July 02, 2018 inspection <br /> Violation #305 -VPH monitoring of the interstitial spaces of the UST system is not maintained. <br /> The S3-87 Vapor sensor was not under vacuum while the inspector was on site. The interstitial space of the UST <br /> shall be maintained, as designed, under constant vacuum such that a breach in the primary or secondary <br /> containment is detected before the hazardous substance is released into the environment. Correct immediately by <br /> having a properly licensed, trained, and certified contractor replace the failed component with a functional <br /> component (LG 113-x listed, if applicable) and obtain a permit within one business day from the EHD if necessary. <br /> If the failed component can't be replaced immediately, there is a possibility that the UST system may be red tagged <br /> to prevent fuel inputs. <br /> Open violations from June 01, 2018 inspection <br /> Violation#101 - Failure to obtain a valid permit to operate from the EHD including but not limited to unpaid <br /> fees. <br /> A permit to operate the UST system has not been issued. No person may own or operate an UST unless a permit <br /> for its operation has been issued by the local agency to the owner or operator of the UST system. Immediately <br /> obtain a permit to operate a UST system from the EHD. An "Operating without a Permit" penalty applies. <br /> Violation#206 -Failure to comply with UST operating permit conditions. <br /> Based on the work orders and the alarm history reviewed two cold starts were conducted on the truck side and EHD <br /> was not notified of this cold starts. One cold start was conducted on 9/11/2017 and another one was conducted on <br /> 10/7/2017. Also 87 mechanical line leak detector on the auto zone was replaced on 1/26/18 without notifying EHD. <br /> No notification of these"cold starts" or replacement of the 87 line leak detector was provided to EHD prior or post <br /> these cold starts and the 87 line leak detector replacement, nor was a repair permit obtained. Obtain the permit from <br /> the EHD for these"cold starts" and line leak detector replacement. Emergency repairs relating to UST system <br /> monitoring and release detection may be performed by a properly licensed, trained, and certified contractor <br /> pursuant to the EHD'S policy and a notification shall be submitted or a permit(if required) shall be obtained within <br /> one business day from the EHD. All other repairs must have a permit submitted to and approved by the EHD prior to <br /> beginning work. Immediately obtain a permit from the EHD for these cold starts. A"Failure to Obtain a Permit" <br /> penalty applies.A copy of the UST operating permit was not found on site. A copy of the UST operating permit and <br /> all attachments and conditions shall be retained at the facility. Immediately obtain a copy of the permit and retain it <br /> on site. <br /> Violation#301 -UST system is not operated to prevent unauthorized release, including spills and overfills. <br /> Fuel filters were observed outside of all under dispenser containments of the auto side at the facility. The <br /> underground storage tank system shall be operated to prevent unauthorized releases. Immediately contact a <br /> properly licensed, trained, and certified contractor to replace or upgrade the component under permit and inspection <br /> with the EHD <br /> Open violations from May 01, 2018 inspection <br /> Violation#101 - Failure to obtain a valid permit to operate from the EHD including but not limited to unpaid <br /> fees. <br /> Due to outstanding violations, a permit to operate the UST system has not been issued for 2018. No person may <br /> own or operate an UST unless a permit for its operation has been issued by the local agency to the owner or <br /> operator of the UST system. Immediately obtain a permit to operate a UST system from the EHD. An "Operating <br /> without a Permit" penalty applies. <br /> Open violations from July 01, 2014 inspection <br /> Page 1 of 1 <br />