Laserfiche WebLink
J • egrAty Tank Tesftg Sydom., lric- <br /> i TTS Int <br /> TEST DATA AND <br /> TEST RESULTS <br /> January 29 , 1988 <br /> Mr. Tom Maragliano <br /> MM s M Ditching f�Ci 2 � 198 <br /> 775 West Second Street <br /> Stockton , California 95206 <br /> Dear Mr. Maragliano : <br /> Following is a summary of the precision testing we recently <br /> conducted onyour underground storage tank(s ) . <br /> Fuclosed are copies or the test worksheets and graphs gene- <br /> rared for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the. loss is less than . 05 <br /> gallons per one hour of testing . If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST <br /> IN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK HPARAMETERS <br /> East 1 , 500 Diesel +. 00367 <br /> West 1, 000 Gasoline +. 01265 Yes <br /> Yes <br /> Fiease contact us if you nee,i additional assistance or <br /> ornation. <br /> ,ir_cerely , <br /> i <br /> r <br /> rank Kea r <br /> Certifie ester <br /> 800 262-6378 166 Pr=k West Circle Stockton, CA 95206 <br />