Laserfiche WebLink
1 clearance, UFC § 11. 201 (b) . <br /> ( ) . <br /> 2 b) Individual containers not marked or labeled, <br /> 3 UFC § 80 . 103 (e) . <br /> 4 c) Lack of secondary containment for the gold <br /> 5 bath and nickel bath area. <br /> 6 d) No cover plate for open electrical box, UFC <br /> 7 § 80 . 301 (1) . <br /> 8 5) Bath Tank Area <br /> g a) No cover plate for open electrical box on <br /> 10 south wall, UFC § 80 . 301 (1) . <br /> 11 b) Bath tanks not labeled, UFC § 80 . 104 (e) . <br /> 12 c) Liquids within the secondary containment <br /> 13 area have to be removed, UFC § 80 . 104 . <br /> 14 6) Outside Area <br /> 15 a) Open container of acid and stored in <br /> 16 improper section, UFC § 80 . 301 (e) . <br /> 17 b) Separation berms are needed to separate the <br /> 18 acids, oxidizers, corrosives and waste <br /> 19 products. Eighteen-inch separation berm <br /> 20 needed between each incompatible material, <br /> 21 UFC § 80. 301 (1) . <br /> 22 c) Secondary containment insufficient (#2 <br /> 23 tank) <br /> 24 d) Piping on wall to #2 tank and to the large <br /> 25 tank not secured, UFC § 80. 301 (c) . <br /> 26 e) Secondary containment not clean and dry, UFC <br /> 27 § 80. 104 . <br /> 28 f) Cooper sulfate material spilled outside <br /> 7 P4 <br />