Laserfiche WebLink
R.V. Circuits <br /> October 11, 1990 <br /> Page 2 <br /> IV. Plating Room <br /> A. Remove combustibles stored next to hot water <br /> heater. Maintain a 30-inch clearance, UFC, <br /> Section 11 .201(b) . <br /> B. Individual containers shall be conspicuously <br /> marked or labeled. Mark all containers that do <br /> not have markings, UFC, Section 80. 103(e) . <br /> C. Secondary containment needed for the gold bath <br /> and nickel bath area. <br /> D. Need cover plate for open electrical box, UFC, <br /> Section 80 . 301(1) . <br /> V. Bath Tank Area <br /> A. Need cover plate for open electrical box on <br /> south wall . <br /> B. All bath tanks need to be labeled, UFC, Section <br /> 80 . 104 (e) . <br /> C. Liquids held within the secondary containment <br /> area (2 inches) have to be removed. This area is <br /> to be kept clean, UFC, 80 . 104 . <br /> VI . Outside - Back <br /> A. Close open container of acid and store in acid <br /> section. UFC, Section 80 . 301 (e) . <br /> B. Separation berms are needed to separate the <br /> acids, oxidizers , corrosives and waste products . <br /> Install eighteen-inch separation berm between <br /> each incompatible material , UFC , Section <br /> 80. 301( 1) . <br /> C. The secondary containment should hold 110 <br /> percent of the largest container with the <br /> addition of the new tank. The berm wall may not <br /> be large enough ( #2 tank) . <br /> D. Piping on wall to #2 tank and to the large tank <br /> needs to be secured, UFC, Section 80 . 301(c) . <br />