Laserfiche WebLink
Dec281503:56p Jiffy Lube 2497 0 2021663 p.7 <br /> JOB TITLE .Ii�Lu6e raNa�STf W�5 lane Slxklon . . <br /> 30305777.2497 01 CALCUIIQION NO <br /> ORIGINATOR B.GEOATE 4176714 <br /> REVIEWER DATE - <br /> SCALE <br /> SHEETNO. 1 of Z <br /> TANK ANCHORING NOTES AND DETAILS DEC 2 8 201 <br /> ENVIRONME TAL <br /> NOTES: HFAIT14mmoTRA hR <br /> 1. THE 2013 CALIFORNIA BUILDING CODE(CBC) SHALL GOVERN ALL MATERIALS AND <br /> WORKMANSHIP. <br /> 2. STRUCTURAL STEEL CONSTRUCTION SHALL CONFORM TO THE SPECIFICATIONS AS <br /> CONTAINED IN THE 13TH EDITION OF THE AISC MANUAL OF STEEL CONSTRUCTION. <br /> 3. STRUCTURAL SHAPES,BAR AND PLATES SHALL BE STEEL MEETING ASTM A36 <br /> SPECIFICATIONS, UNLESS NOTED OTHERWISE. <br /> 4. WELDING SHALL CONFORM TO AWS D1.1 CODE FOR ARC AND GAS WELDING IN BUILDING <br /> CONSTRUCTION.ALL WELD FILLER MUST HAVE MINIMUM 70 KSI TENSILE STRENGTH. <br /> WELDING SHALL BE CONDUCTED BY WELDERS CERTIFIED BY THE AWS. MINIMUM <br /> FILLET WELD SHALL BE 3116'. ALL EXPOSED WELDS SHALL BE GROUND SMOOTH. <br /> 5. SPECIAL INSPECTION SHALL BE PROVIDED PER CBC CHAPTER 17. <br /> 6. ANCHOR BOLTS SHALL BE: <br /> A. HILT[-RE 500-SD EXPDXY ANCHOR WITH 1/2" DIA HAS ROD,2-112"MIN EMBEDMENT. <br /> (MINIMUM EDGE DISTANCE IS 4') <br /> 7 Sti <br /> 'i Pg.34 I <br /> 1 <br />