Laserfiche WebLink
0 <br /> SAN .70AQU'1N LOCAL I-IAz.TH I�2 STRI CT <br /> 9AMPLIkig PROTOCAL FOR ROUTINE TANK ,REMUVALS <br /> The following represents minimum samppling criterion required for closure compliance. If <br /> contamination is documented during closure, an Unauthorized Release notification must be <br /> filled out and submitted to SJLHD within 5 days. Section 2652, CCR. <br /> WATER NOT PRESENT IN THE TANK PIT <br /> TANK SIZE MINIMUM NUM]M Z OF LOCATION OF SOIL SAMPLES <br /> SOIL-SAMPLES <br /> VI'Less than 1000 gallons . ONE per tank') Fill or pump end of tank <br /> 1000 - 10,000 gallons TWO per tank One at each end of tank <br /> 10,001 gallons and up THREE OR MORE Ends and Middle or <br /> pt:x tankenerall spaced aloe <br /> ?he length of the tank <br /> Piping SONE EVERY 20 LINEAL FEET J <br /> WATER IS PRE-SENT IN I&W PIT <br /> TANK SIZE MINIMUM NO. OF LOCATION OF SOIL MINIMUM NUMBER <br /> SOIL SAMPLES SAMPLES OF WATER SAMPLES <br /> 10,000 GALLONS From wall next to <br /> OR LESS tank ends at soil/ <br /> (Single Tank) TWO groundwater ONE <br /> interface <br /> GREATER THAN From wall next to ONE <br /> 10,000 GALLONS tank ends at soil/ <br /> OR groundwater <br /> TANK CLUSTER FOUR interface <br />