AOL AWL <br />SAN JOAQUIN COUNTY 9I, I g6gp 0935 Oa 71 p7o('?3 <br />ENVIRONMENTAL HEALTH DEPARTMENT /Ytct.iW b/.2 7// r—/3 <br />1868 East Hazelton Avenue, Stockton, California 95205-6232 <br />Telephone: (209) 468-3420 Fax: (209) 468-3433 Web: www.sogoy.org/ehd <br />UNDERGROUND STORAGE TANK (UST) PROGRAM INSPECTION REPORT <br />Name: Jims' 24 HR Gas'N Go <br />Addl,'Bss; 8203 East Highway 26, Stockton <br />ection <br />DatInse: Jun 26, 2014 <br />Facility <br />Contact; James Michael Associates, LLC <br />Title: <br />Tanks/Prop owner <br />-803-5026 <br />Inspection <br />Type: <br />XRoutine ❑ Monitoring System Certification U Installation U Complaint -IDrk U Other: <br />(Authority HSC 25288) <br />Consent for: ❑Inspection ❑Sampling ❑Photos <br />owner cannot be reached <br />Granted by: Title: <br />ne <br />Panel:l: Veeder-Root TLS -350 <br />Pa <br />Piping <br />System: 5£Pressurized ❑Suction 0Gravity <br />Overfi ll <br />prevention: $Mechanical UAudiblelvisual <br />- -usT - - <br />Product <br />-----4 ---- - <br />87 -octane <br />- - 5 - - - <br />99 -octane <br />- — 6 --- <br />DSL <br />-------------- <br />------------- <br />- <br />----------- <br />_ <br />Designated <br />Operator: <br />ICC Exp. <br />Date: <br />Violations: U Mi -Release Detection ❑ M2 -Release Prevention 0143 -Both <br />On Site Service <br />Technician: <br />ICC Exp. Manufacturer's <br />Date: Training: <br />VIOLATIONS <br /># <br />C7 C2 <br />M <br />Coda Section <br />HSC = California Health and Safe Code; CCR = California Code of Regulations <br />C1 = Class 1 violation; C2 = Class 2 violation: M = Minor violation <br />- <br />i File Review <br />101 X <br />HSC 25284 <br />No permit to operate <br />102 X <br />HSC 25404.5 <br />Annual operating fees not paid <br />103 <br />HSC 25284(a)(3) <br />No written agreement between the person that the operating permit was issued to and the tank operator to <br />monitor the tank system <br />104 X <br />HSC 25292.2 <br />Current financial responsibility documents not on file with the Environmental Health Department (EHD) <br />105 X <br />CCR 2711 <br />Current Unified Program Consolidated Forms not on file with the EHO (Facility and tank fonn) <br />106 X <br />CCR 2632(b) <br />Monitoring Program (Monitoring & Response Plans) is not current or approved by the EHD <br />107 <br />CCR 2632(d)(1)(C) <br />Plot plan/site map not submitted or fails to completely show where monitoring is performed <br />108 X <br />CCR 2637 <br />Secondary containment: (a) lest not performed; (e) test report not submitted within 30 days; (f) test notification <br />not provided to the EHD at least 48 hours prior to conducting the test <br />109 X <br />CCR 2638 <br />Monitoring equipment certification: (a) not performed annually; (d) test report not submitted within 30 days; <br />(e) test notification not provided to the EHD at least 48 hours prior to conducting an installation, repair, <br />replacement, calibration, or certification <br />110 X <br />HSC 25291(f) <br />Annual line leak detector test not performed (Mi) <br />111 X <br />HSC 25284.2 <br />Annual spill containment testing not performed <br />112 <br />CCR 2636(f)(4) <br />Annual line tightness test not performed if positive shutdown or fail safe not present (M1) <br />113 X <br />CCR 2715(a) <br />Failed to inform the EHD of a change of designated operator within 30 days <br />114 <br />CCR 2715(b) <br />Designated operator does not possess a current ICC CA UST System Operator certification <br />115 <br />CCR 2660(k) <br />Repair for tank or piping not tested for tightness after completion of the repair pursuant to (M2) <br />permit conditions <br />116 <br />HSC 25292.5 <br />Enhanced leak detection (ELD) testing not performed on a system located within 1 000'of public well, or <br />failures not repaired and retested <br />117 <br />CCR 2661 <br />Permit to repair UST system not obtained <br />118 X <br />HSC 25286(a) <br />Operational permit not amended when UST storage and/or monitoring system changed <br />119 <br />HSC 25298(b) <br />Permit to temporarily close UST system not obtained <br />120 X <br />HSC 25298(c) <br />Permit to close UST system not obtained <br />On Site Records <br />201 X <br />CCR 2712(b) <br />Maintenance & monitoring records not maintained 3 years, cathodic protection records for 6 % years, written <br />performance claims pertaining to release detection systems for 5 years, or records of repairs, linings, and <br />upgrades for the life of the tank. Monitoring records include: (1) date and time of all monitoring or sampling; <br />(2) monitoring equipment calibration and maintenance records; (3) results of any visual observations; (4) <br />results of sample analysis performed a lab or in the field; (5) logs of all readings of gauges or other monitoring <br />equipment, round water elevations, or other test results; 6 results of inventory readings and reconciliations <br />202 X <br />CCR 2712(i) <br />Monitoring plan, response plan, and/or operating permit and all conditions not onsite <br />203 <br />CCR 2650 <br />Unauthorized release that: (c) did not escape secondary containment and cleaned up within eight hours (M1) <br />was not recorded; (e) escaped secondary containment, not cleaned up after eight hours, or a sudden loss of <br />product was not reported to the EHD Within 24 hours <br />Inspector - Rea ; 1t tm il <br />Jeffrey Wong (209) 468-0335�o Z7�� <br />EHD 23-02 Rev 04/19/12 Page i UST INSPECTION REPORT <br />