Laserfiche WebLink
Associat C- C4Er-: v irorimer-1ta3�0, Syst ems <br /> P. O. Box 80427 <br /> Bakersfield, CA 93308 <br /> (805) 326-0173 <br /> AES - SYSTEM II <br /> PRECISION TANK & LINE TEST RESULTS SUMMARY <br /> Invoice Address : Tank Location : W. O. #: 18632 <br /> CITY OF TRACY TRACY POLICE DEPT. I. D. Number: N/A <br /> 520 TRACY BLVD 400 E 10TH Technician :FIDB <br /> TRACY CA. 95376 TRACY CA. Tech. #:93-230 Van#:0117 <br /> Date: 12-07-93 Time Start : 12:30 End : 15:00 County : SJ <br /> Facility Phone#: 209-836-4420 Groundwater Depth : 221 Blue Prints : N/A <br /> Contact : DON MASSON Date ;Time system was filled: 12 HR. + <br /> Tank Fill/Vent Product Type Of Vapor Inches of Pump Tank <br /> Tank Capacity Product Tank Vapor Lines Line Recovery Water/Tank Type Material <br /> 1 1000 DSL PASS PASS PASS N/A 0 SUCT SWS <br /> 2 <br /> 3 <br /> 4 <br /> 5 <br /> 6 <br /> Additional Information: THIS IS A 2 HR. FULL SYSTEM' S TEST, WATER TABLE IS <br /> AT 22' PER SJ COUNTY HEALTH DEPT, ALL LINES ARE FLOODED AND INCLUDED IN <br /> TEST. <br /> SITE LOG TIME <br /> Set Up Equip: 12:00 <br /> Bled Product Lines : 12: 15 <br /> Bled Vapor Lines : OPEN <br /> Bled Vent lines : OPEN <br /> Bled Turbine : N/A <br /> Bled Suction Pump: 12:20 <br /> Risers Installed : YES <br /> a) This system and method meets or exceeds the criteria in USEPA 40CFR <br /> part 280, NFPA 329-87 and all applicable state and local codes. <br /> b) Any failure listed above may require further action, check with <br /> all regulatory agencies. <br /> Copyright (c) 1989 by RES, Inc. <br /> a,/J B <br /> Certified Technician Signature : �� ABED 9�" Date <br />