Laserfiche WebLink
REPORT of 'SOILTEST' PRECISION TANK TEST <br />Customer: Amador Stage Lines Date: 3/7/88 <br />Address: Lincoln @ French Camp City: Stockton <br />Product Type: Diesel 42 Tank Gallons: 5050 Tank 4: ASL -2 <br />Test Results - 60 Minute Temperature Comparison <br />Starting Time For Temperature Check 9:15 —Completion Time 10:15 <br />1. Weighted Temperature - Finish = 64.8671 <br />2. Weighted Temperature - Start ....................... <br />64.8791 <br />( ---- <br />3. Weighted Temperature Change 2 from 1) .............. = .-.0120 <br />4. Volume Change for Each Degree of Temperature Change = 2.290 <br />----------- <br />5. Volume Change Due To Temperature (3 x 4)............ _ -.027/-.035 <br />(-ev FielcQ 12 ,o,-'f� �hcF�u./�w..6�hrck vol. cG�a�.� ----------- <br />Test Results - 60 Minute Volume Comparison <br />Starting Time For Volume..... Check 9:15 - Completion Time 10:15 <br />6. Volume of Product Added (-) or Removed (+) During the test <br />to Return "Test Level Indicator" to Starting Point = . -.024 <br />7. Net Gain or Loss .................................... <br />Change sign line 5 and add to line 6 mathmatically.. = +.011 <br />Therefore, since the tested tank had a loss/gain of +,011 gallons <br />per hour, during the time period and on the date above discribed, it <br />DOES/DOES NOT meet the NFPA criterion for tank tightness. <br />B. Comments: Tanks ASL -1, ASL -2, ASL -3 are plumbed together, testes <br />--------------------------------------------------------- <br />as one tank, temperature checked on all tanks, volume on ASL -1. <br />-------------------------------------------------------------------- <br />-----------------------------------=--------------------------------- <br />All of the information used to determine the above results is true <br />and accurate to the best of my knowledge and has been developed by <br />using methods and procedures of the 'SOILTEST Tank 'Tegrity Tester" <br />Certified Technician <br />